LIEBERT-GP-FLEXIBLE-CONDITIONS-MIB DEFINITIONS ::= BEGIN

IMPORTS
    MODULE-IDENTITY, 
    OBJECT-IDENTITY 
        FROM SNMPv2-SMI
    liebertFlexibleConditionsModuleReg 
        FROM LIEBERT-GP-REGISTRATION-MIB
    lgpFlexConditions
        FROM LIEBERT-GP-CONDITIONS-MIB
   ;

-- =============================================================================
-- Module Identification and Registration
-- =============================================================================

liebertGlobalProductsFlexibleConditionsModule MODULE-IDENTITY
  LAST-UPDATED "201810020000Z"
  ORGANIZATION "Liebert Corporation"
  CONTACT-INFO
      "Contact:   Technical Support

      Postal:
      Liebert Corporation
      1050 Dearborn Drive
      P.O. Box 29186
      Columbus OH, 43229
      US

      Tel: +1 (800) 222-5877

      E-mail: liebert.monitoring@vertivco.com
      Web:    www.vertivco.com"

   DESCRIPTION
      "The MIB module used to register Liebert SNMP OIDs.

      Copyright 2000-2018 Liebert Corporation. All rights reserved.
      Reproduction of this document is authorized on the condition
      that the forgoing copyright notice is included.

      This Specification is supplied 'AS IS' and Liebert Corporation
      makes no warranty, either express or implied, as to the use,
      operation, condition, or performance of the Specification."

   REVISION "201810020000Z"
   DESCRIPTION
    "Compiled From GDD Version: 6825.1"


   ::= { liebertFlexibleConditionsModuleReg 1 }

-- =============================================================================
--  lgpFlexConditions - Liebert Conditions Registrations
-- =============================================================================

lgpFlexConditionsWellKnown OBJECT IDENTIFIER
    -- STATUS      current
    -- DESCRIPTION
    --    "Liebert well known conditions are defined by OIDs that
    --    reside in this sub-tree."
    ::= { lgpFlexConditions 1 }

-- =============================================================================
-- lgpFlexConditionsWellKnown - Liebert "well-known" Conditions
-- =============================================================================

lgpCondId4122SystemInputPowerProblem  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The input is not qualified to provide power to the system."
    ::= { lgpFlexConditionsWellKnown 4122 }

lgpCondId4132BypassOverloadPhaseA  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An overload exists on output phase A while operating on the bypass."
    ::= { lgpFlexConditionsWellKnown 4132 }

lgpCondId4133BypassOverloadPhaseB  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An overload exists on output phase B while operating on the bypass."
    ::= { lgpFlexConditionsWellKnown 4133 }

lgpCondId4134BypassOverloadPhaseC  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An overload exists on output phase C while operating on the bypass."
    ::= { lgpFlexConditionsWellKnown 4134 }

lgpCondId4135BypassNotAvailable  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A problem associated with the bypass has been detected."
    ::= { lgpFlexConditionsWellKnown 4135 }

lgpCondId4137BypassAutoRetransferPrimed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Automatic retransfer from bypass to inverter is possible."
    ::= { lgpFlexConditionsWellKnown 4137 }

lgpCondId4138BypassAutoRetransferFailed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "After performing a recoverable transfer to bypass, an attempt to
        auto retransfer from bypass to inverter failed."
    ::= { lgpFlexConditionsWellKnown 4138 }

lgpCondId4139BypassExcessAutoRetransfers  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The number of auto retransfers, from bypass to inverter, has
        exceeded the maximum for a specified time interval."
    ::= { lgpFlexConditionsWellKnown 4139 }

lgpCondId4140BypassRestartInhibitExternal  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Restart of the bypass is inhibited by the state of an external
        signal."
    ::= { lgpFlexConditionsWellKnown 4140 }

lgpCondId4141BypassBreakerClosed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The bypass breaker is closed."
    ::= { lgpFlexConditionsWellKnown 4141 }

lgpCondId4142BypassStaticSwitchOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Bypass off due to static switch overload."
    ::= { lgpFlexConditionsWellKnown 4142 }

lgpCondId4143BypassStaticSwitchUnavailable  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The static bypass is unavailable to support the critical load."
    ::= { lgpFlexConditionsWellKnown 4143 }

lgpCondId4144BypassExcessivePulseParallel  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has performed too many pulse parallel operations within
        a specified time interval."
    ::= { lgpFlexConditionsWellKnown 4144 }

lgpCondId4145BypassAutoTransferFailed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An automatic transfer to static bypass failed."
    ::= { lgpFlexConditionsWellKnown 4145 }

lgpCondId4146SystemInputPhsRotationError  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The power conductors on the input line are not wired to the UPS in
        the sequence preferred for the rectifier (A-B-C)."
    ::= { lgpFlexConditionsWellKnown 4146 }

lgpCondId4147SystemInputCurrentLimit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The RMS input current has reached the input current limit
        threshold."
    ::= { lgpFlexConditionsWellKnown 4147 }

lgpCondId4162BatteryLow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The calculated battery time remaining has reached the low battery
        threshold."
    ::= { lgpFlexConditionsWellKnown 4162 }

lgpCondId4163OutputOffEndofDischarge  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output turned off due to battery reaching end-of-discharge."
    ::= { lgpFlexConditionsWellKnown 4163 }

lgpCondId4164BatteryChargingError  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery is not charging properly."
    ::= { lgpFlexConditionsWellKnown 4164 }

lgpCondId4165BatteryChargingReducedExtrnl  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Using a reduced battery charging algorithm due to an external
        signal."
    ::= { lgpFlexConditionsWellKnown 4165 }

lgpCondId4166BatteryCapacityLow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery capacity is low."
    ::= { lgpFlexConditionsWellKnown 4166 }

lgpCondId4167OutputOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output is off."
    ::= { lgpFlexConditionsWellKnown 4167 }

lgpCondId4168BatteryDischarging  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery is discharging."
    ::= { lgpFlexConditionsWellKnown 4168 }

lgpCondId4169BatteryTemperatureImbalance  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Excessive temperature differences between battery sensors detected."
    ::= { lgpFlexConditionsWellKnown 4169 }

lgpCondId4170BatteryEqualize  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The rectifier output voltage is increased to equalize the battery
        voltage level."
    ::= { lgpFlexConditionsWellKnown 4170 }

lgpCondId4171BatteryManualTestInProgress  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Manual battery test is in progress."
    ::= { lgpFlexConditionsWellKnown 4171 }

lgpCondId4172BatteryAutoTestInProgress  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Automatic battery test is in progress."
    ::= { lgpFlexConditionsWellKnown 4172 }

lgpCondId4173MainBatteryDisconnectOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Main battery disconnect is open."
    ::= { lgpFlexConditionsWellKnown 4173 }

lgpCondId4174BatteryTemperatureSensorFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A battery temperature sensor fault has been detected."
    ::= { lgpFlexConditionsWellKnown 4174 }

lgpCondId4175BypassFrequencyError  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The bypass frequency is outside the inverter synchronization
        limits."
    ::= { lgpFlexConditionsWellKnown 4175 }

lgpCondId4176BatteryCircuitBreaker1Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 1 is open."
    ::= { lgpFlexConditionsWellKnown 4176 }

lgpCondId4177BatteryBreaker1OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 1 failed to open."
    ::= { lgpFlexConditionsWellKnown 4177 }

lgpCondId4178BatteryBreaker1CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 1 failed to close."
    ::= { lgpFlexConditionsWellKnown 4178 }

lgpCondId4179BatteryCircuitBreaker2Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 2 is open."
    ::= { lgpFlexConditionsWellKnown 4179 }

lgpCondId4180BatteryBreaker2OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 2 failed to open."
    ::= { lgpFlexConditionsWellKnown 4180 }

lgpCondId4181BatteryBreaker2CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 2 failed to close."
    ::= { lgpFlexConditionsWellKnown 4181 }

lgpCondId4182BatteryCircuitBreaker3Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 3 is open."
    ::= { lgpFlexConditionsWellKnown 4182 }

lgpCondId4183BatteryBreaker3OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 3 failed to open."
    ::= { lgpFlexConditionsWellKnown 4183 }

lgpCondId4184BatteryBreaker3CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 3 failed to close."
    ::= { lgpFlexConditionsWellKnown 4184 }

lgpCondId4185BatteryCircuitBreaker4Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 4 is open."
    ::= { lgpFlexConditionsWellKnown 4185 }

lgpCondId4186BatteryBreaker4OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 4 failed to open."
    ::= { lgpFlexConditionsWellKnown 4186 }

lgpCondId4187BatteryBreaker4CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 4 failed to close."
    ::= { lgpFlexConditionsWellKnown 4187 }

lgpCondId4188BatteryCircuitBreaker5Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 5 is open."
    ::= { lgpFlexConditionsWellKnown 4188 }

lgpCondId4189BatteryBreaker5OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 5 failed to open."
    ::= { lgpFlexConditionsWellKnown 4189 }

lgpCondId4190BatteryBreaker5CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 5 failed to close."
    ::= { lgpFlexConditionsWellKnown 4190 }

lgpCondId4191BatteryCircuitBreaker6Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 6 is open."
    ::= { lgpFlexConditionsWellKnown 4191 }

lgpCondId4192BatteryBreaker6OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 6 failed to open."
    ::= { lgpFlexConditionsWellKnown 4192 }

lgpCondId4193BatteryBreaker6CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 6 failed to close."
    ::= { lgpFlexConditionsWellKnown 4193 }

lgpCondId4194BatteryCircuitBreaker7Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 7 is open."
    ::= { lgpFlexConditionsWellKnown 4194 }

lgpCondId4195BatteryBreaker7OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 7 failed to open."
    ::= { lgpFlexConditionsWellKnown 4195 }

lgpCondId4196BatteryBreaker7CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 7 failed to close."
    ::= { lgpFlexConditionsWellKnown 4196 }

lgpCondId4197BatteryCircuitBreaker8Open  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 8 is open."
    ::= { lgpFlexConditionsWellKnown 4197 }

lgpCondId4198BatteryBreaker8OpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 8 failed to open."
    ::= { lgpFlexConditionsWellKnown 4198 }

lgpCondId4199BatteryBreaker8CloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery circuit breaker 8 failed to close."
    ::= { lgpFlexConditionsWellKnown 4199 }

lgpCondId4200BatteryChargingInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery charging is inhibited due to an external inhibit signal."
    ::= { lgpFlexConditionsWellKnown 4200 }

lgpCondId4213SystemShutdownEPO  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System shutdown due to Emergency Power Off (EPO)."
    ::= { lgpFlexConditionsWellKnown 4213 }

lgpCondId4214SystemShutdownREPO  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System shutdown due to Remote Emergency Power Off (REPO)."
    ::= { lgpFlexConditionsWellKnown 4214 }

lgpCondId4215SystemOutputOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system output is off."
    ::= { lgpFlexConditionsWellKnown 4215 }

lgpCondId4216BypassBackfeedDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system detected a voltage on the bypass when none was expected."
    ::= { lgpFlexConditionsWellKnown 4216 }

lgpCondId4217BypassManualXfrInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Manual transfer from inverter to bypass is inhibited - bypass not
        qualified."
    ::= { lgpFlexConditionsWellKnown 4217 }

lgpCondId4218BypassManualRexfrInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Manual transfer from bypass to inverter is inhibited - inverter
        output not qualified."
    ::= { lgpFlexConditionsWellKnown 4218 }

lgpCondId4219BatteryOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A battery temperature sensor is reporting a value above a
        threshold."
    ::= { lgpFlexConditionsWellKnown 4219 }

lgpCondId4220BatteryExternalMonitor1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "External battery monitor 1 - battery maintenance required."
    ::= { lgpFlexConditionsWellKnown 4220 }

lgpCondId4221BatteryExternalMonitor2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "External battery monitor 2 - battery maintenance required."
    ::= { lgpFlexConditionsWellKnown 4221 }

lgpCondId4222BatteryGroundFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery system ground fault amperage exceeds the threshold."
    ::= { lgpFlexConditionsWellKnown 4222 }

lgpCondId4229EmergencyPowerOffLatched  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System output is off - 'Emergency Power Off (EPO) - latched'
        requires manual reset."
    ::= { lgpFlexConditionsWellKnown 4229 }

lgpCondId4230SystemOutputLowPowerFactor  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system output power factor is low, resulting in reduced output
        capacity."
    ::= { lgpFlexConditionsWellKnown 4230 }

lgpCondId4231OutputCurrentExceedsThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output current for one or more phases exceeds a threshold."
    ::= { lgpFlexConditionsWellKnown 4231 }

lgpCondId4233InverterFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter failure - inverter output is off."
    ::= { lgpFlexConditionsWellKnown 4233 }

lgpCondId4234InverterOverloadPhaseA  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter is operating with an overload on phase A."
    ::= { lgpFlexConditionsWellKnown 4234 }

lgpCondId4235InverterOverloadPhaseB  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter is operating with an overload on phase B."
    ::= { lgpFlexConditionsWellKnown 4235 }

lgpCondId4236InverterOverloadPhaseC  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter is operating with an overload on phase C."
    ::= { lgpFlexConditionsWellKnown 4236 }

lgpCondId4237InverterInhibitExternal  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Restart of the inverter is inhibited by an external signal."
    ::= { lgpFlexConditionsWellKnown 4237 }

lgpCondId4238InverterOutBreakerOpenFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter output breaker failed to open."
    ::= { lgpFlexConditionsWellKnown 4238 }

lgpCondId4239InverterOutBreakerCloseFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter output breaker failed to close."
    ::= { lgpFlexConditionsWellKnown 4239 }

lgpCondId4270InputContact01  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 1."
    ::= { lgpFlexConditionsWellKnown 4270 }

lgpCondId4271InputContact02  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 2."
    ::= { lgpFlexConditionsWellKnown 4271 }

lgpCondId4272InputContact03  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 3."
    ::= { lgpFlexConditionsWellKnown 4272 }

lgpCondId4273InputContact04  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 4."
    ::= { lgpFlexConditionsWellKnown 4273 }

lgpCondId4274InputContact05  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 5."
    ::= { lgpFlexConditionsWellKnown 4274 }

lgpCondId4275InputContact06  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 6."
    ::= { lgpFlexConditionsWellKnown 4275 }

lgpCondId4276InputContact07  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 7."
    ::= { lgpFlexConditionsWellKnown 4276 }

lgpCondId4277InputContact08  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 8."
    ::= { lgpFlexConditionsWellKnown 4277 }

lgpCondId4278InputContact09  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 9."
    ::= { lgpFlexConditionsWellKnown 4278 }

lgpCondId4279InputContact10  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 10."
    ::= { lgpFlexConditionsWellKnown 4279 }

lgpCondId4280InputContact11  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 11."
    ::= { lgpFlexConditionsWellKnown 4280 }

lgpCondId4281InputContact12  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 12."
    ::= { lgpFlexConditionsWellKnown 4281 }

lgpCondId4282InputContact13  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 13."
    ::= { lgpFlexConditionsWellKnown 4282 }

lgpCondId4283InputContact14  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 14."
    ::= { lgpFlexConditionsWellKnown 4283 }

lgpCondId4284InputContact15  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 15."
    ::= { lgpFlexConditionsWellKnown 4284 }

lgpCondId4285InputContact16  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external input contact 16."
    ::= { lgpFlexConditionsWellKnown 4285 }

lgpCondId4286OutputAmpOverUserLimitPhsA  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The phase A output has exceeded the user amperage threshold."
    ::= { lgpFlexConditionsWellKnown 4286 }

lgpCondId4287OutputAmpOverUserLimitPhsB  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The phase B output has exceeded the user amperage threshold."
    ::= { lgpFlexConditionsWellKnown 4287 }

lgpCondId4288OutputAmpOverUserLimitPhsC  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The phase C output has exceeded the user amperage threshold."
    ::= { lgpFlexConditionsWellKnown 4288 }

lgpCondId4289InverterTransferInhibitExt  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Transfer of critical bus source to inverter is inhibited by an
        external signal."
    ::= { lgpFlexConditionsWellKnown 4289 }

lgpCondId4290InverterShutdownOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The inverter has shutdown due to a sustained overload."
    ::= { lgpFlexConditionsWellKnown 4290 }

lgpCondId4294InletAirOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The inlet air exceeds the maximum temperature threshold."
    ::= { lgpFlexConditionsWellKnown 4294 }

lgpCondId4295RectifierFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Rectifier failure - rectifier is off."
    ::= { lgpFlexConditionsWellKnown 4295 }

lgpCondId4296RectifierOperationInhibitExt  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The operation of the rectifier is inhibited by an external signal."
    ::= { lgpFlexConditionsWellKnown 4296 }

lgpCondId4297UPSOutputonInverter  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output power is supplied by the inverter."
    ::= { lgpFlexConditionsWellKnown 4297 }

lgpCondId4298UPSOutputonBypass  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output power is supplied by the bypass."
    ::= { lgpFlexConditionsWellKnown 4298 }

lgpCondId4299OutputLoadonMaintBypass  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output power is supplied by the maintenance bypass."
    ::= { lgpFlexConditionsWellKnown 4299 }

lgpCondId4300InternalCommunicationsFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The control has detected a communication failure of a component on
        the internal communication bus."
    ::= { lgpFlexConditionsWellKnown 4300 }

lgpCondId4308DCBusGroundFaultPositive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A ground fault has been detected on the positive DC Bus link."
    ::= { lgpFlexConditionsWellKnown 4308 }

lgpCondId4309DCBusGroundFaultNegative  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A ground fault has been detected on the negative DC Bus link."
    ::= { lgpFlexConditionsWellKnown 4309 }

lgpCondId4310EquipmentOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Equipment over temperature summary event."
    ::= { lgpFlexConditionsWellKnown 4310 }

lgpCondId4311SystemFanFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System fan failure - one or more fans have failed."
    ::= { lgpFlexConditionsWellKnown 4311 }

lgpCondId4313PasswordChanged  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Password changed."
    ::= { lgpFlexConditionsWellKnown 4313 }

lgpCondId4314PowerSupplyFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Power supply failure."
    ::= { lgpFlexConditionsWellKnown 4314 }

lgpCondId4315OnGenerator  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A generator is supplying the power to the system."
    ::= { lgpFlexConditionsWellKnown 4315 }

lgpCondId4316AutoRestartInProgress  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Auto restart is in progress."
    ::= { lgpFlexConditionsWellKnown 4316 }

lgpCondId4317AutoRestartInhibitedExt  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Auto restart inhibited due to an external signal."
    ::= { lgpFlexConditionsWellKnown 4317 }

lgpCondId4320InitiatedTransfertoBypass  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "User initiated manual transfer to bypass."
    ::= { lgpFlexConditionsWellKnown 4320 }

lgpCondId4321InitiatedTransfertoInverter  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "User initiated manual transfer to inverter."
    ::= { lgpFlexConditionsWellKnown 4321 }

lgpCondId4322BatteryTestPassed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery test passed."
    ::= { lgpFlexConditionsWellKnown 4322 }

lgpCondId4323BatteryTestFailed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery test failed."
    ::= { lgpFlexConditionsWellKnown 4323 }

lgpCondId4324BatteryTestManuallyStopped  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery test was manually stopped prior to completion."
    ::= { lgpFlexConditionsWellKnown 4324 }

lgpCondId4325BackfeedBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The backfeed breaker is in the open position."
    ::= { lgpFlexConditionsWellKnown 4325 }

lgpCondId4341VelocityAuthenticationFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Notification of a message rejected by Velocity due to an
        authentication failure."
    ::= { lgpFlexConditionsWellKnown 4341 }

lgpCondId4360ReceptacleOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a receptacle over current condition."
    ::= { lgpFlexConditionsWellKnown 4360 }

lgpCondId4361ReceptacleUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a receptacle under current condition."
    ::= { lgpFlexConditionsWellKnown 4361 }

lgpCondId4382SystemInputCurrentImbalance  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System Input Currents are Imbalanced."
    ::= { lgpFlexConditionsWellKnown 4382 }

lgpCondId4383BypassStaticSwitchOffExtrnl  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Bypass static switch is off due to the state of an external signal."
    ::= { lgpFlexConditionsWellKnown 4383 }

lgpCondId4384BatteryEoDDisconnect  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery disconnect due to end-of-discharge."
    ::= { lgpFlexConditionsWellKnown 4384 }

lgpCondId4389SystemOutputFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A fault has been detected in the system output."
    ::= { lgpFlexConditionsWellKnown 4389 }

lgpCondId4390InverterOffExternal  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter is off (operation is inhibited) due to external signal
        state."
    ::= { lgpFlexConditionsWellKnown 4390 }

lgpCondId4391InverterStaticSwitchSCRShort  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a short across one or more inverter static
        switch Silicon Controlled Rectifiers (SCR)."
    ::= { lgpFlexConditionsWellKnown 4391 }

lgpCondId4392TemperatureSensorError  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more temperature sensors cannot provide a valid temperature
        reading (i.e. sensor failure, wiring failure, sense circuit
        failure, etc)."
    ::= { lgpFlexConditionsWellKnown 4392 }

lgpCondId4406BranchOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition."
    ::= { lgpFlexConditionsWellKnown 4406 }

lgpCondId4407BranchUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition."
    ::= { lgpFlexConditionsWellKnown 4407 }

lgpCondId4416BranchOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition."
    ::= { lgpFlexConditionsWellKnown 4416 }

lgpCondId4417BranchUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition."
    ::= { lgpFlexConditionsWellKnown 4417 }

lgpCondId4421BranchFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more conditions indicate a Branch Receptacle Module failure
        , service is required."
    ::= { lgpFlexConditionsWellKnown 4421 }

lgpCondId4436PDUOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition."
    ::= { lgpFlexConditionsWellKnown 4436 }

lgpCondId4437PDUUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition."
    ::= { lgpFlexConditionsWellKnown 4437 }

lgpCondId4438SystemInternalTemperatureRise  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Excessive temperature rise internal to the system (i.e. difference
        between the output versus input temperature is too large)."
    ::= { lgpFlexConditionsWellKnown 4438 }

lgpCondId4439AutomaticRestartFailed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Automatic restart failed."
    ::= { lgpFlexConditionsWellKnown 4439 }

lgpCondId4440FuseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A summary event indicating one or more fuse failures."
    ::= { lgpFlexConditionsWellKnown 4440 }

lgpCondId4441SystemControllerError  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System controller internal error."
    ::= { lgpFlexConditionsWellKnown 4441 }

lgpCondId4442SystemBreakersOpenFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more breakers in the system failed to open."
    ::= { lgpFlexConditionsWellKnown 4442 }

lgpCondId4448PDUOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition."
    ::= { lgpFlexConditionsWellKnown 4448 }

lgpCondId4449PDUUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition."
    ::= { lgpFlexConditionsWellKnown 4449 }

lgpCondId4468PDUOverCurrentL1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition on line 1."
    ::= { lgpFlexConditionsWellKnown 4468 }

lgpCondId4469PDUOverCurrentL2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition on line 2."
    ::= { lgpFlexConditionsWellKnown 4469 }

lgpCondId4470PDUOverCurrentL3  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module over current condition on line 3."
    ::= { lgpFlexConditionsWellKnown 4470 }

lgpCondId4471PDUUnderCurrentL1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition on line 1."
    ::= { lgpFlexConditionsWellKnown 4471 }

lgpCondId4472PDUUnderCurrentL2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition on line 2."
    ::= { lgpFlexConditionsWellKnown 4472 }

lgpCondId4473PDUUnderCurrentL3  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under current condition on line 3."
    ::= { lgpFlexConditionsWellKnown 4473 }

lgpCondId4492ReceptaclePowerStateOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The receptacle power state changed to the ON state."
    ::= { lgpFlexConditionsWellKnown 4492 }

lgpCondId4493ReceptaclePowerStateOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The receptacle power state changed to the OFF state."
    ::= { lgpFlexConditionsWellKnown 4493 }

lgpCondId4494BranchBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Branch Receptacle Module's input breaker is open."
    ::= { lgpFlexConditionsWellKnown 4494 }

lgpCondId4495DeviceConfigurationChange  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Device Configuration Change."
    ::= { lgpFlexConditionsWellKnown 4495 }

lgpCondId4496BasicDisplayModuleRemoved  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Basic Display Module Removed."
    ::= { lgpFlexConditionsWellKnown 4496 }

lgpCondId4497BasicDisplayModuleDiscovered  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Basic Display Module Discovered."
    ::= { lgpFlexConditionsWellKnown 4497 }

lgpCondId4500PDUOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a power module over current condition."
    ::= { lgpFlexConditionsWellKnown 4500 }

lgpCondId4501PDUUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a power module under current condition."
    ::= { lgpFlexConditionsWellKnown 4501 }

lgpCondId4502PDUFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more conditions indicate a power module failure, service is
        required."
    ::= { lgpFlexConditionsWellKnown 4502 }

lgpCondId4503PDUCommunicationFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Internal communications failure with the Power Module."
    ::= { lgpFlexConditionsWellKnown 4503 }

lgpCondId4504BranchRemoved  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Branch Receptacle Module Removed."
    ::= { lgpFlexConditionsWellKnown 4504 }

lgpCondId4505BranchDiscovered  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Branch Receptacle Module Discovered."
    ::= { lgpFlexConditionsWellKnown 4505 }

lgpCondId4506BranchOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a Branch Receptacle Module over current
        condition."
    ::= { lgpFlexConditionsWellKnown 4506 }

lgpCondId4507BranchCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a Branch Receptacle Module under current
        condition."
    ::= { lgpFlexConditionsWellKnown 4507 }

lgpCondId4508ReceptacleLoadRemoved  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The receptacle's load stopped drawing power."
    ::= { lgpFlexConditionsWellKnown 4508 }

lgpCondId4509ReceptacleLoadAdded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The receptacle's load started to draw power."
    ::= { lgpFlexConditionsWellKnown 4509 }

lgpCondId4523ModuleRemoved  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Module Removed."
    ::= { lgpFlexConditionsWellKnown 4523 }

lgpCondId4524ModuleAdded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Module Added."
    ::= { lgpFlexConditionsWellKnown 4524 }

lgpCondId4550FirmwareUpdateRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Module compatibility error requires a system firmware update to
        resolve."
    ::= { lgpFlexConditionsWellKnown 4550 }

lgpCondId4551GenericTestEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A generic test event designed to evaluate system handling of
        events."
    ::= { lgpFlexConditionsWellKnown 4551 }

lgpCondId4580OverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An over temperature condition was detected."
    ::= { lgpFlexConditionsWellKnown 4580 }

lgpCondId4581UnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An under temperature condition was detected."
    ::= { lgpFlexConditionsWellKnown 4581 }

lgpCondId4588OverRelativeHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An over relative humidity condition was detected."
    ::= { lgpFlexConditionsWellKnown 4588 }

lgpCondId4589UnderRelativeHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An under relative humidity condition was detected."
    ::= { lgpFlexConditionsWellKnown 4589 }

lgpCondId4601ExternalAirSensorAOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Ext Air Sensor A Temperature] has exceeded [External Air Over
        Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 4601 }

lgpCondId4604ExternalAirSensorBOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Ext Air Sensor B Temperature] has exceeded [External Air Over
        Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 4604 }

lgpCondId4608ExtAirSensorAUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Ext Air Sensor A Temperature] has dropped below [Ext Air Under
        Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 4608 }

lgpCondId4611ExtAirSensorBUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Ext Air Sensor B Temperature] has dropped below [Ext Air Under
        Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 4611 }

lgpCondId4615ExtDewPointOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "At least one dew point temperature reading ([Ext Air Sensor A Dew
        Point Temp], [Ext Air Sensor B Dew Point Temp]...) has exceeded
        [Ext Dew Point Over Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 4615 }

lgpCondId4618ExternalAirSensorAIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external air sensor A is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 4618 }

lgpCondId4621ExternalAirSensorBIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external air sensor B is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 4621 }

lgpCondId4626SupplyChilledWaterOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Fluid Temperature] has exceeded [High Supply Fluid
        Temperature Threshold]."
    ::= { lgpFlexConditionsWellKnown 4626 }

lgpCondId4629SupplyChilledWaterTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The supply chilled water temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 4629 }

lgpCondId4634SupplyRefrigerantOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Event that is activated when [Supply Refrigerant Temperature]
        exceeds [Supply Refrig Over Temp Threshold]. The event is
        deactivated when the temperature drops below the threshold."
    ::= { lgpFlexConditionsWellKnown 4634 }

lgpCondId4637SupplyRefrigerantUnderTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Refrigerant Temperature] has dropped below a specified
        threshold."
    ::= { lgpFlexConditionsWellKnown 4637 }

lgpCondId4640SupplyRefrigerantTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The supply refrigeramt temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 4640 }

lgpCondId4645SupplyFluidOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Fluid Temperature] has exceeded [Supply Fluid Over Temp
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 4645 }

lgpCondId4648SupplyFluidUnderTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Fluid Temperature] has dropped below a specified threshold."
    ::= { lgpFlexConditionsWellKnown 4648 }

lgpCondId4651SupplyFluidTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The supply fluid temperature sensor is disconnected or the signal
        is out of range."
    ::= { lgpFlexConditionsWellKnown 4651 }

lgpCondId4656Pump1LossofFlow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Loss of flow is detected in pump 1. The loss of flow condition
        occurs when no differential pressure is detected across the pump."
    ::= { lgpFlexConditionsWellKnown 4656 }

lgpCondId4659Pump2LossofFlow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Loss of flow is detected in pump 2. The loss of flow condition
        occurs when no differential pressure is detected across the pump."
    ::= { lgpFlexConditionsWellKnown 4659 }

lgpCondId4662PumpShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pumps have short cycled. A short cycle is defined as turning on
        and off a number of times over a set time period."
    ::= { lgpFlexConditionsWellKnown 4662 }

lgpCondId4669Compressor1AHighHeadPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1A high head pressure."
    ::= { lgpFlexConditionsWellKnown 4669 }

lgpCondId4672Compressor1BHighHeadPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1B high head pressure."
    ::= { lgpFlexConditionsWellKnown 4672 }

lgpCondId4675Compressor2AHighHeadPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 2A high head pressure."
    ::= { lgpFlexConditionsWellKnown 4675 }

lgpCondId4678Compressor2BHighHeadPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 2B high head pressure."
    ::= { lgpFlexConditionsWellKnown 4678 }

lgpCondId4681Compressor1AShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1A short cycle. A short cycle is defined as turning on
        and off a number of times over a set time period."
    ::= { lgpFlexConditionsWellKnown 4681 }

lgpCondId4684Compressor1BShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1B short cycle. A short cycle is defined as turning on
        and off a number of times over a set time period."
    ::= { lgpFlexConditionsWellKnown 4684 }

lgpCondId4687Compressor2AShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 2A short cycle. A short cycle is defined as turning on
        and off a number of times over a set time period."
    ::= { lgpFlexConditionsWellKnown 4687 }

lgpCondId4690Compressor2BShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 2B short cycle. A short cycle is defined as turning on
        and off a number of times over a set time period."
    ::= { lgpFlexConditionsWellKnown 4690 }

lgpCondId4693Tandem1LowSuctionPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "'Tandem compressors' 1 low suction pressure."
    ::= { lgpFlexConditionsWellKnown 4693 }

lgpCondId4696Tandem2LowSuctionPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "'Tandem compressors' 2 low suction pressure."
    ::= { lgpFlexConditionsWellKnown 4696 }

lgpCondId4703ChilledWaterControlValvePosition  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water valve out of position. Chilled water control valve
        position does not match expected value."
    ::= { lgpFlexConditionsWellKnown 4703 }

lgpCondId4711SystemCondensationDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System condensation detected."
    ::= { lgpFlexConditionsWellKnown 4711 }

lgpCondId4714ShutdownLossOfPower  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System lost power. This event becomes active when the unit is
        powered on following an unexpected loss of power."
    ::= { lgpFlexConditionsWellKnown 4714 }

lgpCondId4720SmokeDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Smoke detected."
    ::= { lgpFlexConditionsWellKnown 4720 }

lgpCondId4723WaterUnderFloor  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Water under the floor is detected."
    ::= { lgpFlexConditionsWellKnown 4723 }

lgpCondId4726ServiceRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit requires servicing."
    ::= { lgpFlexConditionsWellKnown 4726 }

lgpCondId4729FanIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more fans are not operating within their operational
        parameters."
    ::= { lgpFlexConditionsWellKnown 4729 }

lgpCondId4732ReceptacleLoadDropped  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The receptacle's load is not drawing power."
    ::= { lgpFlexConditionsWellKnown 4732 }

lgpCondId4740BatteryAutomaticTestInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Automatic (scheduled) battery tests are inhibited."
    ::= { lgpFlexConditionsWellKnown 4740 }

lgpCondId4741BatterySelfTest  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery self test is in progress."
    ::= { lgpFlexConditionsWellKnown 4741 }

lgpCondId4742BatteryLowShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery disconnect due to end-of-discharge."
    ::= { lgpFlexConditionsWellKnown 4742 }

lgpCondId4747EquipmentTemperatureSensorFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more temperature sensors report a temperature outside of
        the range of expected operation."
    ::= { lgpFlexConditionsWellKnown 4747 }

lgpCondId4749SystemFanFailureRedundant  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Redundant system fan failure."
    ::= { lgpFlexConditionsWellKnown 4749 }

lgpCondId4750MultipleFanFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Multiple fan failure."
    ::= { lgpFlexConditionsWellKnown 4750 }

lgpCondId4753MainControllerFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A Main Controller fault has been detected."
    ::= { lgpFlexConditionsWellKnown 4753 }

lgpCondId4754SystemBreakersCloseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more breakers in the system failed to close."
    ::= { lgpFlexConditionsWellKnown 4754 }

lgpCondId4755InputFilterCycleLock  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The input filter disconnect is open due to exceeding the maximum
        number of cycles."
    ::= { lgpFlexConditionsWellKnown 4755 }

lgpCondId4756ServiceCodeActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Service code is running."
    ::= { lgpFlexConditionsWellKnown 4756 }

lgpCondId4757LBSActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Load Bus Sync option is active."
    ::= { lgpFlexConditionsWellKnown 4757 }

lgpCondId4758LBSInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected that conditions to perform Load Bus Sync
        are not satisfied."
    ::= { lgpFlexConditionsWellKnown 4758 }

lgpCondId4759LeadingPowerFactor  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The leading output Power Factor has fallen below a specified value."
    ::= { lgpFlexConditionsWellKnown 4759 }

lgpCondId4760ControlsResetRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A controls reset is required due to one or more critical settings
        changing."
    ::= { lgpFlexConditionsWellKnown 4760 }

lgpCondId4823ParallelCommWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Parallel communication bus warning."
    ::= { lgpFlexConditionsWellKnown 4823 }

lgpCondId4824SystemCommFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Failure of a device on the multi-module system communication bus."
    ::= { lgpFlexConditionsWellKnown 4824 }

lgpCondId4825LossofRedundancy  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The multi-module collection doesn't have enough modules to satisfy
        the redundancy configuration."
    ::= { lgpFlexConditionsWellKnown 4825 }

lgpCondId4826BPSSStartupInhibit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Bypass Static Switch startup is inhibited."
    ::= { lgpFlexConditionsWellKnown 4826 }

lgpCondId4827MMSTransferInhibit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The critical load can not be manually transferred from inverter to
        bypass."
    ::= { lgpFlexConditionsWellKnown 4827 }

lgpCondId4828MMSRetransferInhibit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The critical load can not be manually retransferred from bypass to
        inverter."
    ::= { lgpFlexConditionsWellKnown 4828 }

lgpCondId4830MMSLossofSyncPulse  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Multi-module system loss of sync pulse."
    ::= { lgpFlexConditionsWellKnown 4830 }

lgpCondId4831MMSOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Multi-module system overload."
    ::= { lgpFlexConditionsWellKnown 4831 }

lgpCondId4834MMSOnBattery  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The multi-module system is on battery."
    ::= { lgpFlexConditionsWellKnown 4834 }

lgpCondId4835MMSLowBatteryWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Multi-module system low battery warning."
    ::= { lgpFlexConditionsWellKnown 4835 }

lgpCondId4906LowAmbientTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low ambient temperature condition."
    ::= { lgpFlexConditionsWellKnown 4906 }

lgpCondId4907HighAmbientTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high ambient temperature condition."
    ::= { lgpFlexConditionsWellKnown 4907 }

lgpCondId4908LowOverallVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low battery string overall voltage
        condition."
    ::= { lgpFlexConditionsWellKnown 4908 }

lgpCondId4909HighOverallVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high battery string overall voltage
        condition."
    ::= { lgpFlexConditionsWellKnown 4909 }

lgpCondId4910HighBatteryStringCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high battery string current condition."
    ::= { lgpFlexConditionsWellKnown 4910 }

lgpCondId4911LowBatteryStringFloatCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low battery string float current
        condition."
    ::= { lgpFlexConditionsWellKnown 4911 }

lgpCondId4912HighBatteryStringFloatCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high battery string float current
        condition."
    ::= { lgpFlexConditionsWellKnown 4912 }

lgpCondId4913HighBatteryStringRippleCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high battery string ripple current
        condition."
    ::= { lgpFlexConditionsWellKnown 4913 }

lgpCondId4914BatteryStringDischargeDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a battery string discharge condition."
    ::= { lgpFlexConditionsWellKnown 4914 }

lgpCondId4915MaximumDischargeTimeExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected an excessive discharge time condition."
    ::= { lgpFlexConditionsWellKnown 4915 }

lgpCondId4916DischargeLowOverallVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low battery string overall voltage
        condition during a discharge."
    ::= { lgpFlexConditionsWellKnown 4916 }

lgpCondId4917DischargeLowCellVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low cell voltage condition during a
        discharge."
    ::= { lgpFlexConditionsWellKnown 4917 }

lgpCondId4918DischargeHighBatteryStringCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high battery string current condition
        during a discharge."
    ::= { lgpFlexConditionsWellKnown 4918 }

lgpCondId4919ExcessiveCelltoCellTemperatureDeviation  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected an excessive cell to cell temperature
        deviation condition."
    ::= { lgpFlexConditionsWellKnown 4919 }

lgpCondId4920ExcessiveCelltoAmbientTemperatureDeviation  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected an excessive cell to ambient temperature
        deviation condition."
    ::= { lgpFlexConditionsWellKnown 4920 }

lgpCondId4964LowCellVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low cell voltage condition."
    ::= { lgpFlexConditionsWellKnown 4964 }

lgpCondId4965HighCellVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high cell voltage condition."
    ::= { lgpFlexConditionsWellKnown 4965 }

lgpCondId4966LowCellTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low cell temperature condition."
    ::= { lgpFlexConditionsWellKnown 4966 }

lgpCondId4967HighCellTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high cell temperature condition."
    ::= { lgpFlexConditionsWellKnown 4967 }

lgpCondId4968LowInternalResistance  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low internal resistance condition."
    ::= { lgpFlexConditionsWellKnown 4968 }

lgpCondId4969HighInternalResistance  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high internal resistance condition."
    ::= { lgpFlexConditionsWellKnown 4969 }

lgpCondId4970HighIntercellResistance  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high intercell resistance condition."
    ::= { lgpFlexConditionsWellKnown 4970 }

lgpCondId4978IntertierResistanceHigh  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high intertier resistance condition."
    ::= { lgpFlexConditionsWellKnown 4978 }

lgpCondId4980SupplyChilledWaterLossofFlow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply chilled water or glycol flow is too low."
    ::= { lgpFlexConditionsWellKnown 4980 }

lgpCondId4983SupplyRefrigOverTempBand1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Refrigerant Temperature] is above the upper threshold
        specified by [Supply Refrig Temp Band 1]."
    ::= { lgpFlexConditionsWellKnown 4983 }

lgpCondId4986SupplyRefrigUnderTempBand1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Refrigerant Temperature] is below the lower threshold
        specified by [Supply Refrig Temp Band 1]."
    ::= { lgpFlexConditionsWellKnown 4986 }

lgpCondId4990SupplyRefrigOverTempBand2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Refrigerant Temperature] is above the upper threshold
        specified by [Supply Refrig Temp Band 2]."
    ::= { lgpFlexConditionsWellKnown 4990 }

lgpCondId4993SupplyRefrigUnderTempBand2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Refrigerant Temperature] is below the lower threshold
        specified by [Supply Refrig Temp Band 2]."
    ::= { lgpFlexConditionsWellKnown 4993 }

lgpCondId4996Inverter1ShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter for pump 1 has short cycled and is temporarily locked out
        from further operation to protect from thermal overload. A short
        cycle is defined as powering on and off a number of times over a
        set time period."
    ::= { lgpFlexConditionsWellKnown 4996 }

lgpCondId4999Inverter2ShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter for pump 2 has short cycled and is temporarily locked out
        from further operation to protect from thermal overload. A short
        cycle is defined as powering on and off a number of times over a
        set time period."
    ::= { lgpFlexConditionsWellKnown 4999 }

lgpCondId5015SupplyAirOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Air Temperature] has exceeded [High Supply Air Temperature
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 5015 }

lgpCondId5019SupplyAirUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Supply Air Temperature] has dropped below [Low Supply Air
        Temperature Threshold]."
    ::= { lgpFlexConditionsWellKnown 5019 }

lgpCondId5023ReturnAirOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Air Temperature] has exceeded [High Return Air Temperature
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 5023 }

lgpCondId5026SupplyAirSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The air sensor at the outlet of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5026 }

lgpCondId5034HighReturnHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Humidity] has exceeded [High Return Humidity Threshold]."
    ::= { lgpFlexConditionsWellKnown 5034 }

lgpCondId5036LowReturnHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Humidity] has dropped below [Low Return Humidity
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 5036 }

lgpCondId5037HumidifierHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Operating hours for the humidifier have exceeded the threshold."
    ::= { lgpFlexConditionsWellKnown 5037 }

lgpCondId5038DehumidifierHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Operating hours for the dehumidifier have exceeded the threshold."
    ::= { lgpFlexConditionsWellKnown 5038 }

lgpCondId5039HumidifierUnderCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The electrical current to the humidifier has dropped below its
        lower threshold."
    ::= { lgpFlexConditionsWellKnown 5039 }

lgpCondId5040HumidifierOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The electrical current to the humidifier has exceeded its upper
        threshold."
    ::= { lgpFlexConditionsWellKnown 5040 }

lgpCondId5041HumidifierLowWater  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The water level in the humidifier has dropped below its threshold."
    ::= { lgpFlexConditionsWellKnown 5041 }

lgpCondId5042HumidifierCylinderWorn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Humidifier cylinder is not operating properly and needs to be
        replaced."
    ::= { lgpFlexConditionsWellKnown 5042 }

lgpCondId5043HumidifierIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Humidifier issue detected, causing it to be locked out."
    ::= { lgpFlexConditionsWellKnown 5043 }

lgpCondId5044ExtHumidifierLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The humidifier is shut down and disabled by an external input
        signal."
    ::= { lgpFlexConditionsWellKnown 5044 }

lgpCondId5045HumidifierControlBoardNotDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Humidifier control board is required to be connected, but no
        signal is detected."
    ::= { lgpFlexConditionsWellKnown 5045 }

lgpCondId5046ReturnHumidityOutOfProportionalBand  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Humidity] has exceeded the upper limit of
        [Dehumidification Proportional Band], or has dropped below the
        lower limit of [Humidification Proportional Band] ], for an
        extended period of time."
    ::= { lgpFlexConditionsWellKnown 5046 }

lgpCondId5053LossofAirFlow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "No air flow through the unit due to failure of all fans."
    ::= { lgpFlexConditionsWellKnown 5053 }

lgpCondId5054FanHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Operating hours for the unit blower fan have exceeded the
        threshold."
    ::= { lgpFlexConditionsWellKnown 5054 }

lgpCondId5055TopFanIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The top fan is not operating within its normal parameters."
    ::= { lgpFlexConditionsWellKnown 5055 }

lgpCondId5056BottomFanIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The bottom fan is not operating within its normal parameters."
    ::= { lgpFlexConditionsWellKnown 5056 }

lgpCondId5060RemoteSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Remote sensor is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5060 }

lgpCondId5062Compressor1LowSuctionPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1 low suction pressure."
    ::= { lgpFlexConditionsWellKnown 5062 }

lgpCondId5063Compressor1HoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Operating hours for compressor 1 have exceeded the threshold."
    ::= { lgpFlexConditionsWellKnown 5063 }

lgpCondId5064DigScrollComp1TempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Digital scroll compressor 1 temperature sensor is disconnected or
        the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5064 }

lgpCondId5065DigScrollComp1OverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Digital scroll compressor 1 shut off because its head temperature
        has exceeded the upper threshold."
    ::= { lgpFlexConditionsWellKnown 5065 }

lgpCondId5066Compressor1LowPressureTransducerIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1 low pressure transducer is disconnected or the signal
        is out of range."
    ::= { lgpFlexConditionsWellKnown 5066 }

lgpCondId5067ExtCompressorLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The compressor is shut down and disabled by an external input
        signal."
    ::= { lgpFlexConditionsWellKnown 5067 }

lgpCondId5068ReheaterOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The temperature of the reheater has exceeded its threshold."
    ::= { lgpFlexConditionsWellKnown 5068 }

lgpCondId5069ElectricReheater1HoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Operating hours for electric reheater 1 have exceeded the
        threshold."
    ::= { lgpFlexConditionsWellKnown 5069 }

lgpCondId5070ExtReheatLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The reheater is shut down and disabled by an external input signal."
    ::= { lgpFlexConditionsWellKnown 5070 }

lgpCondId5071Condenser1Issue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser 1 is not operating within its normal parameters."
    ::= { lgpFlexConditionsWellKnown 5071 }

lgpCondId5072CondenserVFDIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The condenser fan Variable Frequency Drive is offline."
    ::= { lgpFlexConditionsWellKnown 5072 }

lgpCondId5073CondenserTVSSIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The condenser Transient Voltage Surge Suppressor or Surge
        Protection Device has failed."
    ::= { lgpFlexConditionsWellKnown 5073 }

lgpCondId5104ExtOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A temperature has exceeded its threshold, as indicated by an
        external input signal."
    ::= { lgpFlexConditionsWellKnown 5104 }

lgpCondId5105ExtLossofFlow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Loss of flow is detected, as indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 5105 }

lgpCondId5106ExtCondenserPumpHighWater  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "High water is detected in the condensate pump by the auxiliary
        float, as indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 5106 }

lgpCondId5107ExtStandbyGlycolPumpOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The standby glycol pump is on, as indicated by an external input
        signal."
    ::= { lgpFlexConditionsWellKnown 5107 }

lgpCondId5108ExternalFireDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fire detected, as indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 5108 }

lgpCondId5109UnitOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit was turned on."
    ::= { lgpFlexConditionsWellKnown 5109 }

lgpCondId5110UnitOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit was turned off."
    ::= { lgpFlexConditionsWellKnown 5110 }

lgpCondId5111UnitStandby  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit was placed in standby mode."
    ::= { lgpFlexConditionsWellKnown 5111 }

lgpCondId5112UnitPartialShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An event has occurred requiring some system components to be
        shutdown and disabled."
    ::= { lgpFlexConditionsWellKnown 5112 }

lgpCondId5113UnitShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An event has occurred requiring the unit to be shutdown and
        disabled to prevent damage to the system."
    ::= { lgpFlexConditionsWellKnown 5113 }

lgpCondId5114WaterLeakageDetectorSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The water leakage detector sensor is disconnected or the signal is
        out of range."
    ::= { lgpFlexConditionsWellKnown 5114 }

lgpCondId5115BMSCommunicationsTimeout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Building Management System (or external monitoring system) has not
        communicated with the system within the expected timeframe."
    ::= { lgpFlexConditionsWellKnown 5115 }

lgpCondId5116MaintenanceDue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The calculated maintenance date has been reached."
    ::= { lgpFlexConditionsWellKnown 5116 }

lgpCondId5117MaintenanceCompleted  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Maintenance has been completed on the unit."
    ::= { lgpFlexConditionsWellKnown 5117 }

lgpCondId5118CloggedAirFilter  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Air filter is dirty and needs to be (cleaned or) replaced."
    ::= { lgpFlexConditionsWellKnown 5118 }

lgpCondId5119RAMBatteryIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "RAM or RAM backup battery is not operating correctly."
    ::= { lgpFlexConditionsWellKnown 5119 }

lgpCondId5120MasterUnitCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with master unit has been lost."
    ::= { lgpFlexConditionsWellKnown 5120 }

lgpCondId5121HighPowerShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply to high power components has been shutdown."
    ::= { lgpFlexConditionsWellKnown 5121 }

lgpCondId5126DigScrollComp2OverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Digital scroll compressor 2 shut off because its head temperature
        has exceeded the upper threshold."
    ::= { lgpFlexConditionsWellKnown 5126 }

lgpCondId5144OutputOfUf  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output frequency has exceeded a specified range for a
        specified period of time."
    ::= { lgpFlexConditionsWellKnown 5144 }

lgpCondId5145MMSModuleAlarmActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Active alarm or fault of any module in a multi-module system."
    ::= { lgpFlexConditionsWellKnown 5145 }

lgpCondId5146CompressorPumpDownIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unable to pump down suction-side pressure during compressor
        shutdown."
    ::= { lgpFlexConditionsWellKnown 5146 }

lgpCondId5147ReturnAirSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The air sensor at the inlet of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5147 }

lgpCondId5148CompressorHighPressureTransducerIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor high pressure transducer is disconnected or the signal
        is out of range."
    ::= { lgpFlexConditionsWellKnown 5148 }

lgpCondId5149BatteryNotQualified  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPS battery voltage is not qualified. This event will be
        detected even in the absence of battery disconnect or when it is
        open."
    ::= { lgpFlexConditionsWellKnown 5149 }

lgpCondId5150BatteryTerminalsReversed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The measured battery voltage is a negative value due to reverse
        battery terminal connections."
    ::= { lgpFlexConditionsWellKnown 5150 }

lgpCondId5151BatteryConverterFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery converter failure. This is a summary event caused by one
        or more power sub-modules in a UPS module."
    ::= { lgpFlexConditionsWellKnown 5151 }

lgpCondId5152InverterSCROpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected an open across one or more inverter static
        switch Silicon Controlled Rectifiers."
    ::= { lgpFlexConditionsWellKnown 5152 }

lgpCondId5153LoadSharingFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Difference between any phase inverter current of unit and the
        relevant average output current of parallel system is more than a
        specific percent of nominal current."
    ::= { lgpFlexConditionsWellKnown 5153 }

lgpCondId5154DCBusAbnormal  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected an abnormal DC Bus Voltage."
    ::= { lgpFlexConditionsWellKnown 5154 }

lgpCondId5155MainsInputNeutralLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Loss of neutral in the input source is detected."
    ::= { lgpFlexConditionsWellKnown 5155 }

lgpCondId5156LoadImpactTransfer  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "On bypass as result of load impact."
    ::= { lgpFlexConditionsWellKnown 5156 }

lgpCondId5157UserOperationInvalid  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "User attempted an invalid operation."
    ::= { lgpFlexConditionsWellKnown 5157 }

lgpCondId5158PowerSubModuleFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more failures detected in power module, inverter or
        rectifier."
    ::= { lgpFlexConditionsWellKnown 5158 }

lgpCondId5178OutputOvervoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the output phase voltages has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5178 }

lgpCondId5179OutputUndervoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the output phase voltages has dropped below the
        limit."
    ::= { lgpFlexConditionsWellKnown 5179 }

lgpCondId5180OutputOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the phase currents has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5180 }

lgpCondId5181NeutralOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system's neutral current has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5181 }

lgpCondId5182GroundOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System ground current has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5182 }

lgpCondId5183OutputVoltageTHD  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Total Harmonic Distortion of the voltage on one or more of the
        output phases has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5183 }

lgpCondId5184OutputFrequencyError  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output frequency is outside a specified range."
    ::= { lgpFlexConditionsWellKnown 5184 }

lgpCondId5185TransformerOvertemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Indicates a unit transformer overtemperature condition."
    ::= { lgpFlexConditionsWellKnown 5185 }

lgpCondId5212PanelSummaryStatus  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The status for the panel. Detects and annunciates upon occurrence
        of any branch or panelboard main breaker active event."
    ::= { lgpFlexConditionsWellKnown 5212 }

lgpCondId5213PanelOvervoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the phase voltages of this panel has exceeded the
        limit."
    ::= { lgpFlexConditionsWellKnown 5213 }

lgpCondId5214PanelUndervoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the phase voltages of this panel is less than the
        limit."
    ::= { lgpFlexConditionsWellKnown 5214 }

lgpCondId5215PanelOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the phase currents of this panel has exceeded the
        limit."
    ::= { lgpFlexConditionsWellKnown 5215 }

lgpCondId5216PanelNeutralOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Neutral current of this panel has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5216 }

lgpCondId5217PanelGroundOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Ground current of this panel has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5217 }

lgpCondId5226BranchOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The current in one or more phases of this branch exceeds the limit."
    ::= { lgpFlexConditionsWellKnown 5226 }

lgpCondId5227BranchUndercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The current in one or more phases of this branch is less than the
        limit."
    ::= { lgpFlexConditionsWellKnown 5227 }

lgpCondId5245SubfeedPhaseOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the phase currents in this subfeed has exceeded the
        limit."
    ::= { lgpFlexConditionsWellKnown 5245 }

lgpCondId5246SubfeedNeutralOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Neutral current in this subfeed has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5246 }

lgpCondId5247SubfeedGroundOvercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Ground current of this subfeed has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5247 }

lgpCondId5249EventState  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The present state of this digital event input."
    ::= { lgpFlexConditionsWellKnown 5249 }

lgpCondId5263CompressorNotStopping  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor commanded to stop, but continues to run."
    ::= { lgpFlexConditionsWellKnown 5263 }

lgpCondId5269CompressorHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Compressor Hours] has exceeded [Compressor Hours Threshold]."
    ::= { lgpFlexConditionsWellKnown 5269 }

lgpCondId5270CompressorHighHeadPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor is shut down due to high head pressure."
    ::= { lgpFlexConditionsWellKnown 5270 }

lgpCondId5271CompressorLowSuctionPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor is shut down due to low suction pressure."
    ::= { lgpFlexConditionsWellKnown 5271 }

lgpCondId5272CompressorThermalOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor is shut down due to thermal overload."
    ::= { lgpFlexConditionsWellKnown 5272 }

lgpCondId5273CompressorLowOilPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor low oil pressure."
    ::= { lgpFlexConditionsWellKnown 5273 }

lgpCondId5274CompressorHeadPressureOverThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor head pressure has exceeded an upper threshold."
    ::= { lgpFlexConditionsWellKnown 5274 }

lgpCondId5275CompressorLossofDifferentialPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor is shut down due to low differential pressure."
    ::= { lgpFlexConditionsWellKnown 5275 }

lgpCondId5277CondenserFanIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser fan is not operating within its operational parameters."
    ::= { lgpFlexConditionsWellKnown 5277 }

lgpCondId5278LowCondenserRefrigerantPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Refrigerant pressure in condenser coil is too low."
    ::= { lgpFlexConditionsWellKnown 5278 }

lgpCondId5280LowFluidPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Fluid Pressure] has dropped below a specified threshold."
    ::= { lgpFlexConditionsWellKnown 5280 }

lgpCondId5293ReturnFluidOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Fluid Temperature] has exceeded a specified threshold."
    ::= { lgpFlexConditionsWellKnown 5293 }

lgpCondId5294ReturnFluidUnderTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Fluid Temperature] has dropped below a specified threshold."
    ::= { lgpFlexConditionsWellKnown 5294 }

lgpCondId5295ReturnFluidTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The return fluid temperature sensor is disconnected or the signal
        is out of range."
    ::= { lgpFlexConditionsWellKnown 5295 }

lgpCondId5296TeamworkReturnFluidTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The return fluid temperature sensors for all Teamwork units are
        disconnected or the signals are out of range."
    ::= { lgpFlexConditionsWellKnown 5296 }

lgpCondId5297AllPumpsLossofFlow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System is shut down due to loss of flow in all available pumps."
    ::= { lgpFlexConditionsWellKnown 5297 }

lgpCondId5300PumpHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Pump Hours] has exceeded [Pump Hours Threshold]."
    ::= { lgpFlexConditionsWellKnown 5300 }

lgpCondId5306FreeCoolingValveHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Free Cooling Valve Hours] has exceeded [Free Cooling Valve Hours
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 5306 }

lgpCondId5308EvaporatorInletTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The evaporator inlet temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5308 }

lgpCondId5309TeamworkEvaporatorInletTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The evaporator inlet temperature sensors for all Teamwork units
        are disconnected or the signals are out of range."
    ::= { lgpFlexConditionsWellKnown 5309 }

lgpCondId5310EvaporatorFluidFreezeAutoReset  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Evaporator outlet fluid temperature has dropped below the freeze
        threshold. Evaporator has been shut down, but will restart when
        the temperature rises above the threshold."
    ::= { lgpFlexConditionsWellKnown 5310 }

lgpCondId5311EvaporatorFluidFreezeManualResetRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Evaporator outlet fluid temperature has dropped below the freeze
        threshold. Evaporator has been shut down and requires a manual
        reset."
    ::= { lgpFlexConditionsWellKnown 5311 }

lgpCondId5315SubgroupEventOccurredDuringCommunicationLoss  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "While subgroup unit communication was lost, an event occurred on
        the subgroup unit. Please check subgroup unit event log."
    ::= { lgpFlexConditionsWellKnown 5315 }

lgpCondId5335ReturnAirUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Return Air Temperature] has dropped below [Low Return Air
        Temperature Threshold]."
    ::= { lgpFlexConditionsWellKnown 5335 }

lgpCondId5349ExtAirSensorAHighHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Ext Air Sensor A Humidity] has exceeded [Ext Air Sensor A High
        Humidity Threshold]."
    ::= { lgpFlexConditionsWellKnown 5349 }

lgpCondId5351ExtAirSensorALowHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Ext Air Sensor A Humidity] has dropped below [Ext Air Sensor A
        Low Humidity Threshold]."
    ::= { lgpFlexConditionsWellKnown 5351 }

lgpCondId5352CompressorShortCycle  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor short cycle. A short cycle is defined as turning on and
        off a number of times over a set time period."
    ::= { lgpFlexConditionsWellKnown 5352 }

lgpCondId5354DigScrollCompDischargeTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Digital scroll compressor discharge temperature sensor is
        disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5354 }

lgpCondId5355DigScrollCompOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Digital scroll compressor is shut down due to head temperature
        exceeding an upper threshold."
    ::= { lgpFlexConditionsWellKnown 5355 }

lgpCondId5361ExtFreeCoolingLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Free cooling is disabled by an external input signal."
    ::= { lgpFlexConditionsWellKnown 5361 }

lgpCondId5362FreeCoolingTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The free cooling fluid temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5362 }

lgpCondId5365HotWaterHotGasValveHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Hot Water / Hot Gas Valve Hours] has exceeded [Hot Water / Hot
        Gas Valve Hours Threshold]."
    ::= { lgpFlexConditionsWellKnown 5365 }

lgpCondId5368ElectricReheaterHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Electric Reheater Hours] has exceeded [Electric Reheaters Hours
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 5368 }

lgpCondId5376MainFanOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Main fan is shut down due to thermal overload."
    ::= { lgpFlexConditionsWellKnown 5376 }

lgpCondId5377Condenser  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser is not operating within its operational parameters."
    ::= { lgpFlexConditionsWellKnown 5377 }

lgpCondId5415ExtLossofAirBlower  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Loss of air blower is detected, as indicated by an external input
        signal."
    ::= { lgpFlexConditionsWellKnown 5415 }

lgpCondId5416ExtStandbyUnitOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Standby unit is on, as indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 5416 }

lgpCondId5417DigitalOutputBoardNotDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Digital output board is required to be connected, but no signal is
        detected."
    ::= { lgpFlexConditionsWellKnown 5417 }

lgpCondId5418UnitCodeMissing  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit code has not been entered and saved."
    ::= { lgpFlexConditionsWellKnown 5418 }

lgpCondId5419UnitCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Master has lost communication with one or more networked units."
    ::= { lgpFlexConditionsWellKnown 5419 }

lgpCondId5422OvertemperaturePowerOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Power turned off because equipment over temperature limit."
    ::= { lgpFlexConditionsWellKnown 5422 }

lgpCondId5423TooManySensors  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The number of sensors connected to the PDU exceeds the allowable
        limit."
    ::= { lgpFlexConditionsWellKnown 5423 }

lgpCondId5432TransformerOvertemperaturePowerOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output power shutdown due to high transformer temperature."
    ::= { lgpFlexConditionsWellKnown 5432 }

lgpCondId5433TransformerOvertemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Transformer temperature has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5433 }

lgpCondId5434TransformerTemperatureSensorFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Transformer temperature sensor has failed."
    ::= { lgpFlexConditionsWellKnown 5434 }

lgpCondId5436LowAmbientTemperatureProbeTwo  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low ambient temperature condition on
        temperature probe 2."
    ::= { lgpFlexConditionsWellKnown 5436 }

lgpCondId5437HighAmbientTemperatureProbeTwo  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a high ambient temperature condition on
        temperature probe 2."
    ::= { lgpFlexConditionsWellKnown 5437 }

lgpCondId5438ThermalRunawayDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a thermal runaway condition."
    ::= { lgpFlexConditionsWellKnown 5438 }

lgpCondId5439BatteryStringEqualize  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a battery string equalize condition."
    ::= { lgpFlexConditionsWellKnown 5439 }

lgpCondId5440BatteryStringOffline  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected the battery string is offline."
    ::= { lgpFlexConditionsWellKnown 5440 }

lgpCondId5442DischargeLowCellVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a low cell voltage condition during a
        discharge."
    ::= { lgpFlexConditionsWellKnown 5442 }

lgpCondId5447MMSPowerSharing  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A module is not sharing power with the other modules in a multi
        -module system."
    ::= { lgpFlexConditionsWellKnown 5447 }

lgpCondId5453ModuleInStandbyIntelligentParalleling  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Module is placed into standby operation per Intelligent
        Paralleling."
    ::= { lgpFlexConditionsWellKnown 5453 }

lgpCondId5456ECOModeActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Conditions for Activation or Automatic Reactivation have been
        satisfied."
    ::= { lgpFlexConditionsWellKnown 5456 }

lgpCondId5457ECOModeSuspended  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "ECO Mode session is suspended."
    ::= { lgpFlexConditionsWellKnown 5457 }

lgpCondId5458ExcessECOSuspends  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Number of automatic suspensions has exceeded the ECO Mode -
        Maximum Auto Suspensions setting."
    ::= { lgpFlexConditionsWellKnown 5458 }

lgpCondId5471DoorOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An open door was detected."
    ::= { lgpFlexConditionsWellKnown 5471 }

lgpCondId5472DoorSensorDisconnected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Door sensor disconnect detected."
    ::= { lgpFlexConditionsWellKnown 5472 }

lgpCondId5479ContactClosureOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An open circuit was detected."
    ::= { lgpFlexConditionsWellKnown 5479 }

lgpCondId5480ContactClosureClosed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A closed circuit was detected."
    ::= { lgpFlexConditionsWellKnown 5480 }

lgpCondId5492ExtSystemCondensationDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "External system condensation detected."
    ::= { lgpFlexConditionsWellKnown 5492 }

lgpCondId5495ExtFanIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more fans are not operating within their operational
        parameters."
    ::= { lgpFlexConditionsWellKnown 5495 }

lgpCondId5500ExtRemoteShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit is shut down by a remote signal."
    ::= { lgpFlexConditionsWellKnown 5500 }

lgpCondId5505HotAisleTempOutofRange  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The air temperature in the Hot aisle is either above [Hot Aisle
        Over Temp Threshold] or below [Hot Aisle Under Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5505 }

lgpCondId5508ColdAisleTempOutofRange  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The air temperature in the cold aisle is either above [Cold Aisle
        Over Temp Threshold] or below [Cold Aisle Under Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5508 }

lgpCondId5512RemoteShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit is shut down by a remote signal."
    ::= { lgpFlexConditionsWellKnown 5512 }

lgpCondId5513CompressorCapacityReduced  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor capacity has been reduced."
    ::= { lgpFlexConditionsWellKnown 5513 }

lgpCondId5514CompressorLowPressureTransducerIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor low pressure transducer is disconnected or the signal
        is out of range."
    ::= { lgpFlexConditionsWellKnown 5514 }

lgpCondId5524PDUNeutralOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a neutral over current condition."
    ::= { lgpFlexConditionsWellKnown 5524 }

lgpCondId5531CondenserCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with condenser unit has been lost."
    ::= { lgpFlexConditionsWellKnown 5531 }

lgpCondId5535CondenserOutsideAirTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser outside air temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5535 }

lgpCondId5536CondenserOutsideAirTempOutofOperatingRange  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Condenser Outside Air Temperature] is either above an upper
        threshold or below a lower threshold."
    ::= { lgpFlexConditionsWellKnown 5536 }

lgpCondId5537CondenserControlBoardIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The condenser control board is reporting an issue."
    ::= { lgpFlexConditionsWellKnown 5537 }

lgpCondId5539CondenserRefrigerantPressureOverThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser refrigerant pressure has exceeded a threshold."
    ::= { lgpFlexConditionsWellKnown 5539 }

lgpCondId5540CondenserRefrigerantPressureUnderThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser refrigerant pressure has dropped below a threshold."
    ::= { lgpFlexConditionsWellKnown 5540 }

lgpCondId5541CondenserRefrigerantPressureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser refrigerant pressure sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5541 }

lgpCondId5542CondenserSupplyRefrigerantOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser supply refrigerant temperature has exceeded a threshold."
    ::= { lgpFlexConditionsWellKnown 5542 }

lgpCondId5543CondenserSupplyRefrigerantUnderTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser supply refrigerant temperature has dropped below a
        specified threshold."
    ::= { lgpFlexConditionsWellKnown 5543 }

lgpCondId5544CondenserSupplyRefrigerantTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser supply refrigerant temperature sensor is disconnected or
        the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5544 }

lgpCondId5545CondenserMaxFanSpeedOverride  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fan speed exceeding the maximum set point in order to alleviate a
        high temperature or pressure condition."
    ::= { lgpFlexConditionsWellKnown 5545 }

lgpCondId5559EvaporatorReturnFluidOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Evaporator Return Fluid Temperature] has exceeded a threshold.
        The event is deactivated when the temperature drops below the
        threshold."
    ::= { lgpFlexConditionsWellKnown 5559 }

lgpCondId5560EvaporatorReturnFluidUnderTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Evaporator Return Fluid Temperature] has dropped below a
        threshold.  The event is deactivated when the temperature rises
        above the threshold."
    ::= { lgpFlexConditionsWellKnown 5560 }

lgpCondId5561LBSActiveMaster  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "This UPS system has been selected as the functional Master Load
        Bus Synchronization (LBS) system."
    ::= { lgpFlexConditionsWellKnown 5561 }

lgpCondId5562LBSActiveSlave  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "This UPS system is synchronized to the output bus of the UPS
        system that has been selected as the Master Load Bus
        Synchronization (LBS) system."
    ::= { lgpFlexConditionsWellKnown 5562 }

lgpCondId5563DCBusLowFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The DC Bus voltage has reached a critical low level."
    ::= { lgpFlexConditionsWellKnown 5563 }

lgpCondId5564FanContactorOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The fan contactor is open."
    ::= { lgpFlexConditionsWellKnown 5564 }

lgpCondId5565FanContactorOpenFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The fan contactor failed to open."
    ::= { lgpFlexConditionsWellKnown 5565 }

lgpCondId5566FanContactorCloseFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The fan contactor failed to close."
    ::= { lgpFlexConditionsWellKnown 5566 }

lgpCondId5567IPInhibit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The intelligent paralleling operation is inhibited."
    ::= { lgpFlexConditionsWellKnown 5567 }

lgpCondId5568InputUndervoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the input phase voltages has dropped below the
        limit."
    ::= { lgpFlexConditionsWellKnown 5568 }

lgpCondId5569InputOvervoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more of the input phase voltages has exceeded the limit."
    ::= { lgpFlexConditionsWellKnown 5569 }

lgpCondId5573AmbientAirSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Ambient air sensor is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5573 }

lgpCondId5577ExtDewPointUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "At least one dew point temperature reading ([Ext Air Sensor A Dew
        Point Temp], [Ext Air Sensor B Dew Point Temp]...) has dropped
        below [Ext Dew Point Under Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5577 }

lgpCondId5578DewPointOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Dew point temperature reading has exceeded the upper threshold."
    ::= { lgpFlexConditionsWellKnown 5578 }

lgpCondId5579DewPointUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Dew point temperature reading has dropped below the lower
        threshold."
    ::= { lgpFlexConditionsWellKnown 5579 }

lgpCondId5588UnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified events active. See local unit display for
        further details."
    ::= { lgpFlexConditionsWellKnown 5588 }

lgpCondId5593RemoteSensorAverageOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Remote Sensor Average Temperature] has exceeded [Remote Sensor
        Over Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5593 }

lgpCondId5594RemoteSensorAverageUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Remote Sensor Average Temperature] has dropped below [Remote
        Sensor Under Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5594 }

lgpCondId5595RemoteSensorSystemAverageOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Remote Sensor System Average Temperature] has exceeded [Remote
        Sensor Over Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5595 }

lgpCondId5596RemoteSensorSystemAverageUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Remote Sensor System Average Temperature] has dropped below
        [Remote Sensor Under Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5596 }

lgpCondId5597RemoteSensorOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Remote Sensor Temperature] has exceeded [Remote Sensor Over Temp
        Threshold]."
    ::= { lgpFlexConditionsWellKnown 5597 }

lgpCondId5598RemoteSensorUnderTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Remote Sensor Temperature] has dropped below [Remote Sensor Under
        Temp Threshold]."
    ::= { lgpFlexConditionsWellKnown 5598 }

lgpCondId5600AirEconomizerEmergencyOverride  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Indoor room temperature has exceeded its upper threshold and the
        outdoor air damper has been opened for emergency cooling."
    ::= { lgpFlexConditionsWellKnown 5600 }

lgpCondId5601AirEconomizerReducedAirflow  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Air economizer filter is dirty and needs to be cleaned or replaced."
    ::= { lgpFlexConditionsWellKnown 5601 }

lgpCondId5604CompressorSuperheatOverThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor discharge refrigerant superheat temperature has
        exceeded an upper threshold."
    ::= { lgpFlexConditionsWellKnown 5604 }

lgpCondId5609ThermalRunawayCelltoAmbientTemperatureEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The delta temperature between a cell temperature and the ambient
        temperature has exceeded the thermal runaway cell to ambient
        temperature threshold."
    ::= { lgpFlexConditionsWellKnown 5609 }

lgpCondId5610ThermalRunawayCelltoCellTemperatureEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The delta temperature between two cells has exceeded the thermal
        runaway cell to cell temperature threshold."
    ::= { lgpFlexConditionsWellKnown 5610 }

lgpCondId5611ThermalRunawayChargerCurrentLevelOneEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Battery-String charger current has exceeded the thermal
        runaway charger current level one threshold."
    ::= { lgpFlexConditionsWellKnown 5611 }

lgpCondId5612ThermalRunawayChargerCurrentLevelTwoEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Battery-String charger current has exceeded the thermal
        runaway charger current level two threshold."
    ::= { lgpFlexConditionsWellKnown 5612 }

lgpCondId5617TemperatureControlSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The air sensor selected for cooling control is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5617 }

lgpCondId5621EEVSuperheatBelowThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic expansion valve refrigerant low superheat event."
    ::= { lgpFlexConditionsWellKnown 5621 }

lgpCondId5622EEVDischargeTempAboveThreshold  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic expansion valve refrigerant high discharge temperature
        event."
    ::= { lgpFlexConditionsWellKnown 5622 }

lgpCondId5623EEVBatteryIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic expansion valve battery cannot be recharged and needs
        to be replaced."
    ::= { lgpFlexConditionsWellKnown 5623 }

lgpCondId5624EEVPowerIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic expansion valve lost power and is running on battery
        backup."
    ::= { lgpFlexConditionsWellKnown 5624 }

lgpCondId5625EEVUnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified electronic expansion valve events active.
        See local unit display for further details."
    ::= { lgpFlexConditionsWellKnown 5625 }

lgpCondId5629StaticPressureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The static pressure sensor is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 5629 }

lgpCondId5630HighStaticPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "High static pressure event."
    ::= { lgpFlexConditionsWellKnown 5630 }

lgpCondId5631LowStaticPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Low static pressure event."
    ::= { lgpFlexConditionsWellKnown 5631 }

lgpCondId5636PumpUnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified pump events active. See local unit display
        for further details."
    ::= { lgpFlexConditionsWellKnown 5636 }

lgpCondId5637CondenserUnitUnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified condenser unit events active. See local
        unit display for further details."
    ::= { lgpFlexConditionsWellKnown 5637 }

lgpCondId5638CondenserCircuitUnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified condenser circuit events active. See local
        unit display for further details."
    ::= { lgpFlexConditionsWellKnown 5638 }

lgpCondId5642SFAReservedEvent1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5642 }

lgpCondId5643SFAReservedEvent2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5643 }

lgpCondId5644SFAReservedEvent3  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5644 }

lgpCondId5645SFAReservedEvent4  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5645 }

lgpCondId5646SFAReservedEvent5  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5646 }

lgpCondId5647SFAReservedEvent6  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5647 }

lgpCondId5648SFAReservedEvent7  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5648 }

lgpCondId5649SFAReservedEvent8  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5649 }

lgpCondId5650SFAReservedEvent9  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5650 }

lgpCondId5651SFAReservedEvent10  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5651 }

lgpCondId5652SFAReservedEvent11  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5652 }

lgpCondId5653SFAReservedEvent12  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5653 }

lgpCondId5654SFAReservedEvent13  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5654 }

lgpCondId5655SFAReservedEvent14  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5655 }

lgpCondId5656SFAReservedEvent15  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5656 }

lgpCondId5657SFAReservedEvent16  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5657 }

lgpCondId5658SFAReservedEvent17  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5658 }

lgpCondId5659SFAReservedEvent18  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5659 }

lgpCondId5660SFAReservedEvent19  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5660 }

lgpCondId5661SFAReservedEvent20  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5661 }

lgpCondId5662SFAReservedEvent21  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5662 }

lgpCondId5663SFAReservedEvent22  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5663 }

lgpCondId5664SFAReservedEvent23  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5664 }

lgpCondId5665SFAReservedEvent24  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5665 }

lgpCondId5666SFAReservedEvent25  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 5666 }

lgpCondId5768OutletAirOvertemperatureLimit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The difference between the outlet air temperature and inlet air
        temperature exceeds a specified maximum temperature."
    ::= { lgpFlexConditionsWellKnown 5768 }

lgpCondId5769EMOShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An Emergency Module Off command has been detected."
    ::= { lgpFlexConditionsWellKnown 5769 }

lgpCondId5770TopOutletFanFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Top outlet fan fault - one or more top outlet fans have failed."
    ::= { lgpFlexConditionsWellKnown 5770 }

lgpCondId5771MMSOverCapacity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The multi-module system load is larger than the apparent power
        limit setting."
    ::= { lgpFlexConditionsWellKnown 5771 }

lgpCondId5773CompressorCapacityNormal  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor has returned to normal load capacity."
    ::= { lgpFlexConditionsWellKnown 5773 }

lgpCondId5774CompressorContactorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor contactor is not closing during compressor startup or
        is not opening during compressor shutdown."
    ::= { lgpFlexConditionsWellKnown 5774 }

lgpCondId5775UnitShutdownUnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified unit shutdown events active. See local
        unit display for further details."
    ::= { lgpFlexConditionsWellKnown 5775 }

lgpCondId5776PDULowVoltageLN  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under voltage condition (LN)."
    ::= { lgpFlexConditionsWellKnown 5776 }

lgpCondId5777PDULowVoltageLL  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under voltage condition (LL)."
    ::= { lgpFlexConditionsWellKnown 5777 }

lgpCondId5778PDULowVoltageL1L2  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line-to-line under voltage condition (L1
        -L2)."
    ::= { lgpFlexConditionsWellKnown 5778 }

lgpCondId5779PDULowVoltageL2L3  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line-to-line under voltage condition (L2
        -L3)."
    ::= { lgpFlexConditionsWellKnown 5779 }

lgpCondId5780PDULowVoltageL3L1  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line-to-line under voltage condition (L3
        -L1)."
    ::= { lgpFlexConditionsWellKnown 5780 }

lgpCondId5781PDULowVoltageL1N  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line to neutral under voltage condition
        (L1-N)."
    ::= { lgpFlexConditionsWellKnown 5781 }

lgpCondId5782PDULowVoltageL2N  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line to neutral under voltage condition
        (L2-N)."
    ::= { lgpFlexConditionsWellKnown 5782 }

lgpCondId5783PDULowVoltageL3N  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line to neutral under voltage condition
        (L3-N)."
    ::= { lgpFlexConditionsWellKnown 5783 }

lgpCondId5784BranchLowVoltageLN  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under voltage condition (LN)."
    ::= { lgpFlexConditionsWellKnown 5784 }

lgpCondId5785BranchLowVoltageLL  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under voltage condition (LL)."
    ::= { lgpFlexConditionsWellKnown 5785 }

lgpCondId5786BranchLowVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under voltage condition."
    ::= { lgpFlexConditionsWellKnown 5786 }

lgpCondId5788ContTieActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Continuous Power Tie Active."
    ::= { lgpFlexConditionsWellKnown 5788 }

lgpCondId5792UserkWhReset  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The user kWh accumulator was reset to zero by the operator."
    ::= { lgpFlexConditionsWellKnown 5792 }

lgpCondId5796PeakkWReset  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Peak kW was reset."
    ::= { lgpFlexConditionsWellKnown 5796 }

lgpCondId5798BypassOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Bypass overloaded, reduce load immediately."
    ::= { lgpFlexConditionsWellKnown 5798 }

lgpCondId5801LowBatteryShutdownImminent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "If active and guaranteed shutdown is enabled, a low battery
        reserve condition exists that will shutdown the UPS."
    ::= { lgpFlexConditionsWellKnown 5801 }

lgpCondId5806OutputOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An overload exists on the output."
    ::= { lgpFlexConditionsWellKnown 5806 }

lgpCondId5807OutputOffPending  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output off pending - shutdown imminent."
    ::= { lgpFlexConditionsWellKnown 5807 }

lgpCondId5808SystemShutdownOutputShort  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Shutdown was due to a short on the output."
    ::= { lgpFlexConditionsWellKnown 5808 }

lgpCondId5809SystemShutdownLowBattery  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Shutdown was due to a low battery condition."
    ::= { lgpFlexConditionsWellKnown 5809 }

lgpCondId5810SystemShutdownRemoteShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Shutdown was due to a remote communications shutdown command."
    ::= { lgpFlexConditionsWellKnown 5810 }

lgpCondId5811SystemShutdownHardwareFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Shutdown was due to an externally applied hardware control signal."
    ::= { lgpFlexConditionsWellKnown 5811 }

lgpCondId5817LossofRedundancy  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has an insufficient number of power modules to provide
        redundancy."
    ::= { lgpFlexConditionsWellKnown 5817 }

lgpCondId5818PowerModuleFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more conditions indicate a power module failure, service is
        required."
    ::= { lgpFlexConditionsWellKnown 5818 }

lgpCondId5819PowerModuleWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more power modules is reporting a warning condition."
    ::= { lgpFlexConditionsWellKnown 5819 }

lgpCondId5838PowerModuleFanFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Power Module has detected a fan fault."
    ::= { lgpFlexConditionsWellKnown 5838 }

lgpCondId5839PowerModuleOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Power Module has detected an over temperature condition."
    ::= { lgpFlexConditionsWellKnown 5839 }

lgpCondId5840PowerModuleShutdownOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Power Module has shutdown due to over temperature."
    ::= { lgpFlexConditionsWellKnown 5840 }

lgpCondId5842ChargerModuleFanFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Charger Module has detected a fan fault."
    ::= { lgpFlexConditionsWellKnown 5842 }

lgpCondId5847BatteryModuleTemperatureSensorFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A Battery Module temperature sensor fault has been detected."
    ::= { lgpFlexConditionsWellKnown 5847 }

lgpCondId5848BatteryModuleOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Battery Module has detected an over temperature condition."
    ::= { lgpFlexConditionsWellKnown 5848 }

lgpCondId5849ReplaceBatteryModule  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Battery Module needs to be replaced."
    ::= { lgpFlexConditionsWellKnown 5849 }

lgpCondId5850SystemShutdownTransformerOverTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "System shutdown due to transformer over temperature."
    ::= { lgpFlexConditionsWellKnown 5850 }

lgpCondId5851MaximumLoadAlarm  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Maximum load alarm indicating load setting has been exceeded."
    ::= { lgpFlexConditionsWellKnown 5851 }

lgpCondId5856BatteryModuleFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more battery modules are reporting a fault condition."
    ::= { lgpFlexConditionsWellKnown 5856 }

lgpCondId5857BatteryModuleWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more battery modules are reporting a warning condition."
    ::= { lgpFlexConditionsWellKnown 5857 }

lgpCondId5862CheckAirFilter  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Please check air filter, it may need to be cleaned or replaced."
    ::= { lgpFlexConditionsWellKnown 5862 }

lgpCondId5863TransformerFanFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The transformer fan has failed."
    ::= { lgpFlexConditionsWellKnown 5863 }

lgpCondId5865NoLoadWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Indicates the UPS has output voltage but the output current is
        below a set threshold [No Load Warning Current Threshold] for a
        set period of time [No Load Warning Delay]."
    ::= { lgpFlexConditionsWellKnown 5865 }

lgpCondId5871BatteryOverTemperatureLimit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A battery temperature sensor is reporting a value above a
        predetermined limit."
    ::= { lgpFlexConditionsWellKnown 5871 }

lgpCondId5873UnexpectedMainBatteryDisconnectClosure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The main battery disconnect has closed unexpectedly."
    ::= { lgpFlexConditionsWellKnown 5873 }

lgpCondId5874BatteryOverVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected that the battery voltage has exceeded a
        predetermined limit."
    ::= { lgpFlexConditionsWellKnown 5874 }

lgpCondId5875BatteryFuseFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more battery fuse faults has occurred."
    ::= { lgpFlexConditionsWellKnown 5875 }

lgpCondId5878MainBatteryDisconnectForcedToUnlock  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The main battery disconnect is forced to the unlocked state."
    ::= { lgpFlexConditionsWellKnown 5878 }

lgpCondId5879VdcBackfeed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The voltage between battery and DC bus measurements is out of
        tolerance."
    ::= { lgpFlexConditionsWellKnown 5879 }

lgpCondId5880RectifierConfigurationChangeRequest  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "This event indicates that the battery is not configured and PFC is
        not enabled."
    ::= { lgpFlexConditionsWellKnown 5880 }

lgpCondId5881RegenerationActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Regeneration operation is active."
    ::= { lgpFlexConditionsWellKnown 5881 }

lgpCondId5882RegenerationOperationTerminated  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Regeneration operation is not active."
    ::= { lgpFlexConditionsWellKnown 5882 }

lgpCondId5883RegenerationOperationFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Regeneration operation has been terminated due to bypass source
        instability or unit misoperation."
    ::= { lgpFlexConditionsWellKnown 5883 }

lgpCondId5884ProgramInputContact01  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 01] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5884 }

lgpCondId5885ProgramInputContact02  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 02] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5885 }

lgpCondId5886ProgramInputContact03  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 03] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5886 }

lgpCondId5887ProgramInputContact04  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 04] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5887 }

lgpCondId5888ProgramInputContact05  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 05] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5888 }

lgpCondId5889ProgramInputContact06  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 06] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5889 }

lgpCondId5890ProgramInputContact07  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 07] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5890 }

lgpCondId5891ProgramInputContact08  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 08] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5891 }

lgpCondId5892ProgramInputContact09  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 09] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5892 }

lgpCondId5893ProgramInputContact10  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 10] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5893 }

lgpCondId5894ProgramInputContact11  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 11] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5894 }

lgpCondId5895ProgramInputContact12  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "When the signal from [Program Input Contact 12] is active the
        function assigned to this contact is executed."
    ::= { lgpFlexConditionsWellKnown 5895 }

lgpCondId5896GroundFaultDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a ground fault on a Battery-String."
    ::= { lgpFlexConditionsWellKnown 5896 }

lgpCondId5902ReturnHumiditySensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The humidity sensor at the inlet of the unit is disconnected or
        the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5902 }

lgpCondId5903CompressorLowDifferentialPressureLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor exceeded maximum startup attempts due to low
        differential pressure. Compressor is shutdown and has been
        disabled."
    ::= { lgpFlexConditionsWellKnown 5903 }

lgpCondId5906AirflowSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Airflow sensor is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 5906 }

lgpCondId5907ExtAirDamperPositionIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Air damper position does not match expected value, as indicated by
        an external input signal."
    ::= { lgpFlexConditionsWellKnown 5907 }

lgpCondId5908ExtPowerSourceAFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit main power source A failure, as indicated by an external
        input signal."
    ::= { lgpFlexConditionsWellKnown 5908 }

lgpCondId5909ExtPowerSourceBFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit main power source B failure, as indicated by an external
        input signal."
    ::= { lgpFlexConditionsWellKnown 5909 }

lgpCondId5910StaticPressureSensorOutofRange  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Static pressure sensor signal is out of its configured range."
    ::= { lgpFlexConditionsWellKnown 5910 }

lgpCondId5911FluidTemperatureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The fluid temperature sensor is disconnected or the signal is out
        of range."
    ::= { lgpFlexConditionsWellKnown 5911 }

lgpCondId5912FluidFlowSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The fluid flow sensor is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 5912 }

lgpCondId5914OverDifferentialPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An over differential pressure condition was detected."
    ::= { lgpFlexConditionsWellKnown 5914 }

lgpCondId5915UnderDifferentialPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An under differential pressure condition was detected."
    ::= { lgpFlexConditionsWellKnown 5915 }

lgpCondId5924MixedModeLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Mixed mode has been entered too many times over a rolling time
        period and has been temporarily disabled.  Mixed mode is defined
        as the use of a compressor on one refrigeration circuit and the
        use of a refrigerant pump on the other circuit."
    ::= { lgpFlexConditionsWellKnown 5924 }

lgpCondId5928UnbalancedLoadCondition  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a line-to-line unbalanced load condition."
    ::= { lgpFlexConditionsWellKnown 5928 }

lgpCondId5939BranchOverCurrentProtection  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Branch Receptacle Module's over current protection is
        triggered."
    ::= { lgpFlexConditionsWellKnown 5939 }

lgpCondId5948BranchLowVoltageLL  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a module under voltage condition (LL)."
    ::= { lgpFlexConditionsWellKnown 5948 }

lgpCondId5957BypassInputVoltageFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected the bypass voltage is unqualified."
    ::= { lgpFlexConditionsWellKnown 5957 }

lgpCondId5958BatteryTemperatureOutofRange  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery temperature is outside of acceptable range."
    ::= { lgpFlexConditionsWellKnown 5958 }

lgpCondId5960InverterOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter in overload fault."
    ::= { lgpFlexConditionsWellKnown 5960 }

lgpCondId5966AuxAirTempDeviceCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with external auxiliary device providing an air
        temperature value has been lost."
    ::= { lgpFlexConditionsWellKnown 5966 }

lgpCondId5967ModbusPowerMeterCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with Modbus power meter has been lost."
    ::= { lgpFlexConditionsWellKnown 5967 }

lgpCondId5968InverterDesaturation  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Inverter Desaturation."
    ::= { lgpFlexConditionsWellKnown 5968 }

lgpCondId5969GenericDICFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The control board reports a fault - Service required."
    ::= { lgpFlexConditionsWellKnown 5969 }

lgpCondId5970GroundFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An AC phase to ground fault or three phase fault to ground exists
        on the output of the UPS."
    ::= { lgpFlexConditionsWellKnown 5970 }

lgpCondId5973InputBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The main input breaker is open."
    ::= { lgpFlexConditionsWellKnown 5973 }

lgpCondId5974NeutralBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The neutral breaker is open."
    ::= { lgpFlexConditionsWellKnown 5974 }

lgpCondId5975OutputBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output breaker is open."
    ::= { lgpFlexConditionsWellKnown 5975 }

lgpCondId5976MaintenanceBypassBreakerClosed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The maintenance bypass breaker is closed."
    ::= { lgpFlexConditionsWellKnown 5976 }

lgpCondId5977BatteryBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery circuit is open."
    ::= { lgpFlexConditionsWellKnown 5977 }

lgpCondId5978RectifierIsolationBreakerRFBOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The rectifier isolation breaker (RFB) indicates that it is in the
        open position."
    ::= { lgpFlexConditionsWellKnown 5978 }

lgpCondId5982BypassBreakerSBBOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The bypass circuit breaker (SBB) indicates that it is in the open
        position."
    ::= { lgpFlexConditionsWellKnown 5982 }

lgpCondId5983BypassIsolationBreakerBIBOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The bypass isolation breaker (BIB) indicates that it is in the
        open position."
    ::= { lgpFlexConditionsWellKnown 5983 }

lgpCondId5984BypassUndervoltageWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The voltage on one or more bypass phases is less than a specified
        percentage of the nominal voltage."
    ::= { lgpFlexConditionsWellKnown 5984 }

lgpCondId5985BypassStaticSwitchBPSSOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Bypass Static Switch has been turned on."
    ::= { lgpFlexConditionsWellKnown 5985 }

lgpCondId5998BattOvtempWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A battery temperature sensor is reporting a value above the
        setpoint."
    ::= { lgpFlexConditionsWellKnown 5998 }

lgpCondId6009InverterOutputBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The inverter output breaker indicates that it is in the open
        position."
    ::= { lgpFlexConditionsWellKnown 6009 }

lgpCondId6011EquipmentOverTempWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Equipment over temperature warning is a summary event based on the
        detection of at least one measured temperature exceeding a
        threshold."
    ::= { lgpFlexConditionsWellKnown 6011 }

lgpCondId6012EquipmentOvertemperatureLimit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The equipment air temperature has exceeded its maximum set point."
    ::= { lgpFlexConditionsWellKnown 6012 }

lgpCondId6045RectifierInputBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The rectifier isolation breaker indicates that it is in the open
        position."
    ::= { lgpFlexConditionsWellKnown 6045 }

lgpCondId6046LoadonUPS  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The output is being supplied power from the inverter."
    ::= { lgpFlexConditionsWellKnown 6046 }

lgpCondId6047Core2CoreFuseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Core-2-core fuse failure."
    ::= { lgpFlexConditionsWellKnown 6047 }

lgpCondId6052SystemOutputBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system output breaker is open."
    ::= { lgpFlexConditionsWellKnown 6052 }

lgpCondId6059InverterRelayFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The inverter relay has malfunctioned."
    ::= { lgpFlexConditionsWellKnown 6059 }

lgpCondId6060TransfertoBypassSystemOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPS System has transferred to bypass because the active power
        modules cannot support the critical load."
    ::= { lgpFlexConditionsWellKnown 6060 }

lgpCondId6061InputSourceBackfeed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery is backfeeding the input source."
    ::= { lgpFlexConditionsWellKnown 6061 }

lgpCondId6062LossofSynchronization  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The inverter and bypass are no longer synchronized. ."
    ::= { lgpFlexConditionsWellKnown 6062 }

lgpCondId6063BatteryConverterCurrentLimit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery converter has reached is maximum current limit.  ."
    ::= { lgpFlexConditionsWellKnown 6063 }

lgpCondId6064LBSCableFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Load Bus Sync communications is abnormal. A problem with the LBS
        cable may exist."
    ::= { lgpFlexConditionsWellKnown 6064 }

lgpCondId6065BatteryChargeEqualizationTimeout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery equalizing is time out."
    ::= { lgpFlexConditionsWellKnown 6065 }

lgpCondId6066ParallelCableFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPS parallel system communications is abnormal. A problem with
        the parallel cable may exist."
    ::= { lgpFlexConditionsWellKnown 6066 }

lgpCondId6067BatteryFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A short circuit exists in the battery system."
    ::= { lgpFlexConditionsWellKnown 6067 }

lgpCondId6068BatteryRoomAlarm  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The ambient temperature of the battery room is abnormal."
    ::= { lgpFlexConditionsWellKnown 6068 }

lgpCondId6080UPSCCommunicationFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPSC has failed to communicate in a designated time period."
    ::= { lgpFlexConditionsWellKnown 6080 }

lgpCondId6092Compressor1BThermalOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fixed compressor 1B is shut down due to thermal overload."
    ::= { lgpFlexConditionsWellKnown 6092 }

lgpCondId6093Compressor2BThermalOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fixed compressor 2B is shut down due to thermal overload."
    ::= { lgpFlexConditionsWellKnown 6093 }

lgpCondId6094Compressor1BHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fixed compressor 1B run hours have exceeded the threshold."
    ::= { lgpFlexConditionsWellKnown 6094 }

lgpCondId6095Compressor2BHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fixed compressor 2B run hours have exceeded the threshold."
    ::= { lgpFlexConditionsWellKnown 6095 }

lgpCondId6100CondenserRemoteShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser is shut down by a remote signal."
    ::= { lgpFlexConditionsWellKnown 6100 }

lgpCondId6105ExternalCondenserTVSSIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The condenser Transient Voltage Surge Suppressor or Surge
        Protection Device has failed, as indicated by an external input
        signal."
    ::= { lgpFlexConditionsWellKnown 6105 }

lgpCondId6106ExternalCondenserVFDIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The condenser fan Variable Frequency Drive is offline, as
        indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 6106 }

lgpCondId6107ExternalCondenserIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Condenser is not operating within its operational parameters, as
        indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 6107 }

lgpCondId6119Slotsnotavailable  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The number of sensors exceeds the number of allocated slots and
        cannot be displayed."
    ::= { lgpFlexConditionsWellKnown 6119 }

lgpCondId6180BatteryUnderVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery voltage is too low."
    ::= { lgpFlexConditionsWellKnown 6180 }

lgpCondId6182ReplaceBattery  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The battery is due for replacement."
    ::= { lgpFlexConditionsWellKnown 6182 }

lgpCondId6186InputFrequencyDeviation  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The input frequency is outside of the normal range."
    ::= { lgpFlexConditionsWellKnown 6186 }

lgpCondId6187ShutdownPending  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Shutdown is pending."
    ::= { lgpFlexConditionsWellKnown 6187 }

lgpCondId6194SystemRebootCommandIssued  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reboot command issued to the system."
    ::= { lgpFlexConditionsWellKnown 6194 }

lgpCondId6203SensorAdded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Sensor Added."
    ::= { lgpFlexConditionsWellKnown 6203 }

lgpCondId6204SensorRemoved  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Sensor Removed."
    ::= { lgpFlexConditionsWellKnown 6204 }

lgpCondId6205WaterLeakDetected  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Water leak detected."
    ::= { lgpFlexConditionsWellKnown 6205 }

lgpCondId6210FirmwareUpdateInProgress  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Firmware update has started and is in progress."
    ::= { lgpFlexConditionsWellKnown 6210 }

lgpCondId6211FirmwareUpdateCompletedSuccessfully  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Firmware update has completed successfully."
    ::= { lgpFlexConditionsWellKnown 6211 }

lgpCondId6212FirmwareUpdateCompletedUnsuccessfully  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Firmware update has completed, but was not successful."
    ::= { lgpFlexConditionsWellKnown 6212 }

lgpCondId6216PrechargeCircuitFailed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "DC Bus precharge/discharge didn't reach specified level within a
        specified time."
    ::= { lgpFlexConditionsWellKnown 6216 }

lgpCondId6217MemoryCardRemoved  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The memory card on the control board has been removed."
    ::= { lgpFlexConditionsWellKnown 6217 }

lgpCondId6218AutoCalibrationActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system is automatically calibrating ADC channels."
    ::= { lgpFlexConditionsWellKnown 6218 }

lgpCondId6219AutoCalibrationFailed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "ADC channel calibration has failed."
    ::= { lgpFlexConditionsWellKnown 6219 }

lgpCondId6220ModuleOutputBreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The module output breaker is open."
    ::= { lgpFlexConditionsWellKnown 6220 }

lgpCondId6221NeutralVoltageFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Voltage observed on neutral line."
    ::= { lgpFlexConditionsWellKnown 6221 }

lgpCondId6222BranchLoadLoss  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Loss of load on branch detected. Branch circuit breaker might be
        open."
    ::= { lgpFlexConditionsWellKnown 6222 }

lgpCondId6225RemoteSensorLowHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Remote sensor humidity has dropped below a lower threshold.  The
        event is deactivated when the humidity rises above the threshold."
    ::= { lgpFlexConditionsWellKnown 6225 }

lgpCondId6226RemoteSensorHighHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Remote sensor humidity has exceeded an upper threshold.  The event
        is deactivated when the humidity drops below the threshold."
    ::= { lgpFlexConditionsWellKnown 6226 }

lgpCondId6227RemoteSensorAverageLowHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The average humidity of multiple remote sensors on the cooling
        unit has dropped below a lower threshold.   The event is
        deactivated when the humidity rises above the threshold."
    ::= { lgpFlexConditionsWellKnown 6227 }

lgpCondId6228RemoteSensorAverageHighHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The average humidity of multiple remote sensors on the cooling
        unit has exceeded an upper threshold.   The event is deactivated
        when the humidity drops below the threshold."
    ::= { lgpFlexConditionsWellKnown 6228 }

lgpCondId6229RemoteSensorSystemAverageLowHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The average humidity of multiple remote sensors on interconnected
        cooling units in a single system has dropped below a lower
        threshold.   The event is deactivated when the humidity rises
        above the threshold."
    ::= { lgpFlexConditionsWellKnown 6229 }

lgpCondId6230RemoteSensorSystemAverageHighHumidity  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The average humidity of multiple remote sensors on interconnected
        cooling units in a single system has exceeded an upper threshold.
        The event is deactivated when the humidity drops below the
        threshold."
    ::= { lgpFlexConditionsWellKnown 6230 }

lgpCondId6231LowCompressorSuperheat  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor suction superheat has dropped below a lower threshold."
    ::= { lgpFlexConditionsWellKnown 6231 }

lgpCondId6232SECUnspecifiedGeneralEvent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "One or more unspecified events active for the Superheat and
        Envelope Controller.  See local unit display for further details."
    ::= { lgpFlexConditionsWellKnown 6232 }

lgpCondId6233SECCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with the Superheat and Envelope Controller has been
        lost.  The event is deactivated when communication is re
        -established."
    ::= { lgpFlexConditionsWellKnown 6233 }

lgpCondId6236PowerSourceAIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "No power is detected at power source input 'A'."
    ::= { lgpFlexConditionsWellKnown 6236 }

lgpCondId6237PowerSourceBIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "No power is detected at power source input 'B'."
    ::= { lgpFlexConditionsWellKnown 6237 }

lgpCondId6239FluidValveHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Operating hours for the fluid valve have exceeded the threshold."
    ::= { lgpFlexConditionsWellKnown 6239 }

lgpCondId6253BoosterFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Booster failure - boost is off."
    ::= { lgpFlexConditionsWellKnown 6253 }

lgpCondId6254ChargerFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Charger Failure - Charger is off."
    ::= { lgpFlexConditionsWellKnown 6254 }

lgpCondId6274UnitTopReturnAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Return air sensor at the top of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6274 }

lgpCondId6275UnitMiddleReturnAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Return air sensor in the middle of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6275 }

lgpCondId6276UnitBottomReturnAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Return air sensor at the bottom of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6276 }

lgpCondId6277UnitTopSupplyAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply air sensor at the top of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6277 }

lgpCondId6278UnitMiddleFirstSupplyAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "First supply air sensor in the middle of the unit is disconnected
        or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6278 }

lgpCondId6279UnitBottomSupplyAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply air sensor at the bottom of the unit is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6279 }

lgpCondId6284UnitMiddleSecondSupplyAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Second supply air sensor in the middle of the unit is disconnected
        or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6284 }

lgpCondId6293ChilledWaterControlActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water inlet temperature control function is enabled due to
        'bad' water."
    ::= { lgpFlexConditionsWellKnown 6293 }

lgpCondId6294ChilledWaterFlowTransducerFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water flow transducer is disconnected or the signal is out
        of range."
    ::= { lgpFlexConditionsWellKnown 6294 }

lgpCondId6295ChilledWaterInletTemperatureSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water inlet temperature sensor is disconnected or the
        signal is out of range.   The sensor is mandatory for the chilled
        water flow function."
    ::= { lgpFlexConditionsWellKnown 6295 }

lgpCondId6296ChilledWaterHighInletTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water inlet temperature has exceeded an upper threshold."
    ::= { lgpFlexConditionsWellKnown 6296 }

lgpCondId6297Modbus010VModuleCommunicationFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Modbus 0-10V module for managing the second Chilled Water circuit
        valve is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6297 }

lgpCondId6299RackDoorsOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Rack doors opened due to supply air temperature exceeding the
        [Rack Door Open High Supply Air Temperature Threshold]."
    ::= { lgpFlexConditionsWellKnown 6299 }

lgpCondId6303TeamStaticPressureSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The team static pressure sensor is disconnected or the signal is
        out of range."
    ::= { lgpFlexConditionsWellKnown 6303 }

lgpCondId6304HeatingLockout  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Heating is shut down and disabled."
    ::= { lgpFlexConditionsWellKnown 6304 }

lgpCondId6305FreeCoolingStoppedHighRoomTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Free cooling is temporarily disabled due to room temperature
        exceeding a preset delta above the the set point."
    ::= { lgpFlexConditionsWellKnown 6305 }

lgpCondId6306ColdAisleTemperatureHumidityTeamSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Cold aisle team sensor measuring air temperature and humidity is
        disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6306 }

lgpCondId6309ColdAisleAirSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Cold aisle sensor measuring air temperature and humidity is
        disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6309 }

lgpCondId6310ChilledWaterInletTemperatureControlActive  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water inlet temperature control is active."
    ::= { lgpFlexConditionsWellKnown 6310 }

lgpCondId6313ChilledWaterInletTemperatureSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water inlet temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6313 }

lgpCondId6314ChilledWaterOutletTemperatureSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water outlet temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6314 }

lgpCondId6315ChilledWaterFlowMeterSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Chilled water flow meter sensor is disconnected or the signal is
        out of range."
    ::= { lgpFlexConditionsWellKnown 6315 }

lgpCondId6333Bypassoutofsync  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Bypass and Inverter inputs are not in sync."
    ::= { lgpFlexConditionsWellKnown 6333 }

lgpCondId6348SystemOutputoffasrequested  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPS has shutdown as requested, i.e., the output is off."
    ::= { lgpFlexConditionsWellKnown 6348 }

lgpCondId6349SystemOffasrequested  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The entire UPS has shutdown as commanded."
    ::= { lgpFlexConditionsWellKnown 6349 }

lgpCondId6350GeneralFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A general fault in the UPS has been detected."
    ::= { lgpFlexConditionsWellKnown 6350 }

lgpCondId6351UPSAwaitingPower  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPS output is off and the UPS is awaiting the return of input
        power."
    ::= { lgpFlexConditionsWellKnown 6351 }

lgpCondId6352AutonomyCalibration  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Calibration test occurred."
    ::= { lgpFlexConditionsWellKnown 6352 }

lgpCondId6353GeneralWarning  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A warning in the UPS has been detected."
    ::= { lgpFlexConditionsWellKnown 6353 }

lgpCondId6354BatteryCharging  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The UPS battery is charging (battery charge percentage lower than
        98)."
    ::= { lgpFlexConditionsWellKnown 6354 }

lgpCondId6355BackfeedRelayFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Bypass SCR is wrongly on or commutated."
    ::= { lgpFlexConditionsWellKnown 6355 }

lgpCondId6356BatteryCircuitOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Battery Circuit Open."
    ::= { lgpFlexConditionsWellKnown 6356 }

lgpCondId6357SystemRestartPending  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A request for UPS restart has been received."
    ::= { lgpFlexConditionsWellKnown 6357 }

lgpCondId6358PipeTemperatureSensorFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Air temperature sensor located in the pipe is not sending a valid
        value."
    ::= { lgpFlexConditionsWellKnown 6358 }

lgpCondId6362SFAReservedEvent26  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6362 }

lgpCondId6363SFAReservedEvent27  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6363 }

lgpCondId6364SFAReservedEvent28  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6364 }

lgpCondId6365SFAReservedEvent29  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6365 }

lgpCondId6366SFAReservedEvent30  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6366 }

lgpCondId6367SFAReservedEvent31  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6367 }

lgpCondId6368SFAReservedEvent32  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6368 }

lgpCondId6369SFAReservedEvent33  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6369 }

lgpCondId6370SFAReservedEvent34  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6370 }

lgpCondId6371SFAReservedEvent35  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6371 }

lgpCondId6372SFAReservedEvent36  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6372 }

lgpCondId6373SFAReservedEvent37  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6373 }

lgpCondId6374SFAReservedEvent38  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6374 }

lgpCondId6375SFAReservedEvent39  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6375 }

lgpCondId6376SFAReservedEvent40  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6376 }

lgpCondId6377SFAReservedEvent41  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6377 }

lgpCondId6378SFAReservedEvent42  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6378 }

lgpCondId6379SFAReservedEvent43  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6379 }

lgpCondId6380SFAReservedEvent44  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6380 }

lgpCondId6381SFAReservedEvent45  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6381 }

lgpCondId6382SFAReservedEvent46  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6382 }

lgpCondId6383SFAReservedEvent47  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6383 }

lgpCondId6384SFAReservedEvent48  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6384 }

lgpCondId6385SFAReservedEvent49  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6385 }

lgpCondId6386SFAReservedEvent50  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Reserved event for SFA use."
    ::= { lgpFlexConditionsWellKnown 6386 }

lgpCondId6438PowerModuleInputCurrentAbnormal  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Input current of the power module is abnormal."
    ::= { lgpFlexConditionsWellKnown 6438 }

lgpCondId6439PowerModuleBalancerofDCBusFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Balancer of DC Bus in the power module has failed."
    ::= { lgpFlexConditionsWellKnown 6439 }

lgpCondId6440PowerModuleFuseFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A summary event indicating one or more fuse failures in the power
        module."
    ::= { lgpFlexConditionsWellKnown 6440 }

lgpCondId6441PowerModulePowerSupplyFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Power module power supply failure."
    ::= { lgpFlexConditionsWellKnown 6441 }

lgpCondId6450PDUPoweredOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The PDU was powered on."
    ::= { lgpFlexConditionsWellKnown 6450 }

lgpCondId6453InputWiringFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The neutral/ground conductors on the input wiring are not properly
        bonded, or the line/neutral conductors have been swapped."
    ::= { lgpFlexConditionsWellKnown 6453 }

lgpCondId6454DCtoDCConverterFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A failure has occurred in the battery discharge circuit."
    ::= { lgpFlexConditionsWellKnown 6454 }

lgpCondId6455LeakSensorCableFault  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A fault is detected in the 'Leak Sensor' cable."
    ::= { lgpFlexConditionsWellKnown 6455 }

lgpCondId6518StandbyUnitActivatedDuetoChillerFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "External chiller unit has failed for this unit, so the standby
        cooling unit has been activated."
    ::= { lgpFlexConditionsWellKnown 6518 }

lgpCondId6522PDUResidualOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a PDU residual over current condition."
    ::= { lgpFlexConditionsWellKnown 6522 }

lgpCondId6527PDUOverCurrentProtection  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The PDU over current protection is triggered."
    ::= { lgpFlexConditionsWellKnown 6527 }

lgpCondId6528PowerModuleLeverUnlocked  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The power module is inactive because the lever is in the unlocked
        position."
    ::= { lgpFlexConditionsWellKnown 6528 }

lgpCondId6529HardwareMismatch  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The assigned system model settings do not match the actual
        installed hardware. The module count is wrong, or a module of the
        wrong type is installed."
    ::= { lgpFlexConditionsWellKnown 6529 }

lgpCondId6530SupplyNTCAirSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The supply NTC air sensor is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 6530 }

lgpCondId6531ExternalAirSensorCIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external air sensor C is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 6531 }

lgpCondId6532ExternalAirSensorDIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external air sensor D is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 6532 }

lgpCondId6533ExternalAirSensorEIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The external air sensor E is disconnected or the signal is out of
        range."
    ::= { lgpFlexConditionsWellKnown 6533 }

lgpCondId6534PumpThermalOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump is shut down due to thermal overload."
    ::= { lgpFlexConditionsWellKnown 6534 }

lgpCondId6535XDModuleCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with XD Module has been lost."
    ::= { lgpFlexConditionsWellKnown 6535 }

lgpCondId6536MMSCapacityExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The critical load is larger than the redundant rating of a 1+N
        redundant multi-module system."
    ::= { lgpFlexConditionsWellKnown 6536 }

lgpCondId6538TSAControlInputIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The analog input used to set the air temperature set point for
        cooling control is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6538 }

lgpCondId6539ChilledWaterValveHoursExceeded  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "[Chilled Water Valve Hours] has exceeded [Chilled Water Valve
        Operating Hours Threshold]."
    ::= { lgpFlexConditionsWellKnown 6539 }

lgpCondId6540FSAControlInputIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The analog input used to set the air temperature set point for fan
        speed control is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6540 }

lgpCondId6541AutoTuneLicenseExpiring  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "License for the AutoTune feature has not been refreshed in 30 days
        and will be expiring soon."
    ::= { lgpFlexConditionsWellKnown 6541 }

lgpCondId6542AutoTuneLicenseExpired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "License for the AutoTune feature has expired."
    ::= { lgpFlexConditionsWellKnown 6542 }

lgpCondId6543UnitInStandbyDueToCoolingLoss  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit forced into standby because it is unable to provide any
        cooling."
    ::= { lgpFlexConditionsWellKnown 6543 }

lgpCondId6544ControlUnitsRemoteShutdownMismatch  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The remote shutdown status of the primary control unit does not
        match the remote shutdown status of the secondary control unit."
    ::= { lgpFlexConditionsWellKnown 6544 }

lgpCondId6545SecondaryControlUnitCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The primary control unit has lost Ethernet communications with the
        secondary control unit."
    ::= { lgpFlexConditionsWellKnown 6545 }

lgpCondId6546ControlUnitsUnitCodeMismatch  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit codes for the primary and secondary control units do not
        match."
    ::= { lgpFlexConditionsWellKnown 6546 }

lgpCondId6547SSAControlInputIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The analog input used to set the static pressure set point for fan
        speed control is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6547 }

lgpCondId6574SubfeedPhaseUndercurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Subfeed breaker phase current has dropped below the threshold."
    ::= { lgpFlexConditionsWellKnown 6574 }

lgpCondId6587TransferCountCleared  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A system event indicating the transfer count has been cleared."
    ::= { lgpFlexConditionsWellKnown 6587 }

lgpCondId6588EnergyCounterCleared  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A system event indicating the energy counter (e.g. KWH) has been
        cleared."
    ::= { lgpFlexConditionsWellKnown 6588 }

lgpCondId6589HistoryLogsFull  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The history logs are full."
    ::= { lgpFlexConditionsWellKnown 6589 }

lgpCondId6590HistoryLogsCleared  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "History logs have been cleared."
    ::= { lgpFlexConditionsWellKnown 6590 }

lgpCondId6591EventLogCleared  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "All past alarms and faults have been cleared."
    ::= { lgpFlexConditionsWellKnown 6591 }

lgpCondId6592SystemDateChanged  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system date has been updated."
    ::= { lgpFlexConditionsWellKnown 6592 }

lgpCondId6593SystemTimeChanged  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system time has been updated."
    ::= { lgpFlexConditionsWellKnown 6593 }

lgpCondId6594AccessPasswordChanged  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The access password has been changed."
    ::= { lgpFlexConditionsWellKnown 6594 }

lgpCondId6595ConfigModified  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A setpoint has been updated."
    ::= { lgpFlexConditionsWellKnown 6595 }

lgpCondId6612SCRShort  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The SCR is in a short condition."
    ::= { lgpFlexConditionsWellKnown 6612 }

lgpCondId6613SCROpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The SCR is in an open condition."
    ::= { lgpFlexConditionsWellKnown 6613 }

lgpCondId6614ACPowerSupplyFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A failure of the AC Power Supply has been detected."
    ::= { lgpFlexConditionsWellKnown 6614 }

lgpCondId6615DCPowerSupplyFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A failure of the DC Power Supply has been detected."
    ::= { lgpFlexConditionsWellKnown 6615 }

lgpCondId6616VoltageSensorFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A voltage sensor failure has been detected."
    ::= { lgpFlexConditionsWellKnown 6616 }

lgpCondId6617SCRSensorFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The SCR sensor module failed."
    ::= { lgpFlexConditionsWellKnown 6617 }

lgpCondId6618CurrentSensorFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The current sensor module failed."
    ::= { lgpFlexConditionsWellKnown 6618 }

lgpCondId6619GateDriveFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The Gate Drive module failed."
    ::= { lgpFlexConditionsWellKnown 6619 }

lgpCondId6620SurgeFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The surge module failed for the input source."
    ::= { lgpFlexConditionsWellKnown 6620 }

lgpCondId6621FastUnderVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Fast under voltage detected."
    ::= { lgpFlexConditionsWellKnown 6621 }

lgpCondId6622SlowUnderVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Slow under voltage detected."
    ::= { lgpFlexConditionsWellKnown 6622 }

lgpCondId6623OverVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Over voltage detected."
    ::= { lgpFlexConditionsWellKnown 6623 }

lgpCondId6624OverUnderFrequencyFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An over or under frequency condition has been detected."
    ::= { lgpFlexConditionsWellKnown 6624 }

lgpCondId6625GeneralSourceFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A non-specific failure has been detected in the source."
    ::= { lgpFlexConditionsWellKnown 6625 }

lgpCondId6626OverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "An over current has been detected."
    ::= { lgpFlexConditionsWellKnown 6626 }

lgpCondId6627PeakCurrentOffLimit  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The peak current has exceeded the setpoint defined by I-PK Xfer
        Lockout."
    ::= { lgpFlexConditionsWellKnown 6627 }

lgpCondId6628SyncFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A phase rotation/out of synchronization failure has been detected."
    ::= { lgpFlexConditionsWellKnown 6628 }

lgpCondId6629InputOverVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Input over voltage."
    ::= { lgpFlexConditionsWellKnown 6629 }

lgpCondId6630InputUnderVoltage  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Input under voltage."
    ::= { lgpFlexConditionsWellKnown 6630 }

lgpCondId6631InputOverUnderFrequency  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Input over/under frequency."
    ::= { lgpFlexConditionsWellKnown 6631 }

lgpCondId6635VoltageSenseFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output voltage sense failure."
    ::= { lgpFlexConditionsWellKnown 6635 }

lgpCondId6636LoadonAlternateSource  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The load is on the alternate source."
    ::= { lgpFlexConditionsWellKnown 6636 }

lgpCondId6637UnderVoltageFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output under voltage failure."
    ::= { lgpFlexConditionsWellKnown 6637 }

lgpCondId6638OutputOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Output is over current."
    ::= { lgpFlexConditionsWellKnown 6638 }

lgpCondId6639GroundOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Ground is over current."
    ::= { lgpFlexConditionsWellKnown 6639 }

lgpCondId6640NeutralOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Neutral is over current."
    ::= { lgpFlexConditionsWellKnown 6640 }

lgpCondId6641LoadVoltageTHD  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Load voltage THD has exceeded the set limit."
    ::= { lgpFlexConditionsWellKnown 6641 }

lgpCondId6662ControlLogicFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A control logic module has failed."
    ::= { lgpFlexConditionsWellKnown 6662 }

lgpCondId6663PowerSupplyLogicFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "A power supply module has failed."
    ::= { lgpFlexConditionsWellKnown 6663 }

lgpCondId6664ExternalCommsFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "External communications failure."
    ::= { lgpFlexConditionsWellKnown 6664 }

lgpCondId6665HeatSinkOverTemp  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system heat sink temperature has exceeded design limits."
    ::= { lgpFlexConditionsWellKnown 6665 }

lgpCondId6666AutomaticTransferInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Automatic transfer is inhibited."
    ::= { lgpFlexConditionsWellKnown 6666 }

lgpCondId6667InputSourceTransferInhibited  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Input source transfer is inhibited."
    ::= { lgpFlexConditionsWellKnown 6667 }

lgpCondId6676CB1ShuntTrip  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB1 Shunt Trip event."
    ::= { lgpFlexConditionsWellKnown 6676 }

lgpCondId6677CB2ShuntTrip  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB2 Shunt Trip event."
    ::= { lgpFlexConditionsWellKnown 6677 }

lgpCondId6678CB6NeutralOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB6 neutral open event."
    ::= { lgpFlexConditionsWellKnown 6678 }

lgpCondId6679ContactorNeutralFail  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Contactor Neutral Fail event."
    ::= { lgpFlexConditionsWellKnown 6679 }

lgpCondId6680CB1BreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB1 Breaker open event. Normal state is breaker closed. Latched
        state is breaker open."
    ::= { lgpFlexConditionsWellKnown 6680 }

lgpCondId6681CB2BreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB2 Breaker open event. Normal state is breaker closed. Latched
        state is breaker open."
    ::= { lgpFlexConditionsWellKnown 6681 }

lgpCondId6682CB4BreakerClosed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB4 breaker closed event. Normal state is breaker open. Latched
        state is breaker closed."
    ::= { lgpFlexConditionsWellKnown 6682 }

lgpCondId6683CB5BreakerClosed  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB5 breaker closed event. Normal state is breaker open. Latched
        state is breaker closed."
    ::= { lgpFlexConditionsWellKnown 6683 }

lgpCondId6684CB3BreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB3 breaker open event. Normal state is breaker closed. Latched
        state is breaker open."
    ::= { lgpFlexConditionsWellKnown 6684 }

lgpCondId6685CB3ABreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB3A breaker open event. Normal state is breaker closed. Latched
        state is breaker open."
    ::= { lgpFlexConditionsWellKnown 6685 }

lgpCondId6686CB6BreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB6 breaker open event. Normal state is breaker closed. Latched
        state is breaker open."
    ::= { lgpFlexConditionsWellKnown 6686 }

lgpCondId6687CB7BreakerOpen  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "CB7 breaker open event. Normal state is breaker closed. Latched
        state is breaker open."
    ::= { lgpFlexConditionsWellKnown 6687 }

lgpCondId6691GroupIndependentOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The group standby/cascade state for this unit has been overridden.
        The unit has been forced on."
    ::= { lgpFlexConditionsWellKnown 6691 }

lgpCondId6692GroupIndependentOff  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The group standby/cascade state for this unit has been overridden.
        The unit has been forced off."
    ::= { lgpFlexConditionsWellKnown 6692 }

lgpCondId6693BranchResidualOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a branch residual over current condition."
    ::= { lgpFlexConditionsWellKnown 6693 }

lgpCondId6694ReceptacleResidualOverCurrent  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The system has detected a receptacle residual over current
        condition."
    ::= { lgpFlexConditionsWellKnown 6694 }

lgpCondId6728BuckOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The input voltage is currently being bucked (lowered) by the
        inverter."
    ::= { lgpFlexConditionsWellKnown 6728 }

lgpCondId6729BoostOn  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The input voltage is currently being boosted (raised) by the
        inverter."
    ::= { lgpFlexConditionsWellKnown 6729 }

lgpCondId6739Compressor1HighPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1 High Pressure."
    ::= { lgpFlexConditionsWellKnown 6739 }

lgpCondId6740Compressor2HighPressure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 2 High Pressure."
    ::= { lgpFlexConditionsWellKnown 6740 }

lgpCondId6741Compressor1ThermalOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 1 Thermal Overload."
    ::= { lgpFlexConditionsWellKnown 6741 }

lgpCondId6742Compressor2ThermalOverload  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor 2 Thermal Overload."
    ::= { lgpFlexConditionsWellKnown 6742 }

lgpCondId6758CompressorFreezeProtection  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Compressor has entered the freeze protection phase."
    ::= { lgpFlexConditionsWellKnown 6758 }

lgpCondId6773FanTemperatureCompensationLimitReached  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Unit is configured for fan temperature compensation, and the fan
        control set point cannot be reduced any further due to high
        remote air temperature sensor readings."
    ::= { lgpFlexConditionsWellKnown 6773 }

lgpCondId6774ModbusECFanCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with Modbus EC fan has been lost."
    ::= { lgpFlexConditionsWellKnown 6774 }

lgpCondId6785AnalogTemperatureControlIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Analog input used for creating the control temperature (instead of
        reading a sensor)  is disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6785 }

lgpCondId6786SubgroupFirmwareUpdateRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Mismatch of subgroup firmware.  Both the primary and secondary
        control boards must be running the same firmware version."
    ::= { lgpFlexConditionsWellKnown 6786 }

lgpCondId6787SubgroupSecondaryControlUnitIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Subgroup secondary control unit is reporting an unspecified issue."
    ::= { lgpFlexConditionsWellKnown 6787 }

lgpCondId6788EEVCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with Electronic Expansion Valve unit has been lost."
    ::= { lgpFlexConditionsWellKnown 6788 }

lgpCondId6789EEVMotorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve stepper motor issue."
    ::= { lgpFlexConditionsWellKnown 6789 }

lgpCondId6790EEVFeedbackIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve feedback error."
    ::= { lgpFlexConditionsWellKnown 6790 }

lgpCondId6791EEVPressureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve refrigerant pressure sensor is
        disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6791 }

lgpCondId6792EEVCoilTemperatureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve coil temperature sensor is disconnected
        or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6792 }

lgpCondId6793EEVDischargeTemperatureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve discharge temperature sensor is
        disconnected or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6793 }

lgpCondId6794EEVSumpTemperatureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve sump temperature sensor is disconnected
        or the signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6794 }

lgpCondId6795EEVBatteryTestIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve battery state cannot be determined."
    ::= { lgpFlexConditionsWellKnown 6795 }

lgpCondId6796EEVBatteryPersistentIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Electronic Expansion Valve has continuously detected a 'bad'
        battery condition for an extended period of time."
    ::= { lgpFlexConditionsWellKnown 6796 }

lgpCondId6798PumpCycleLockOut  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump is locked out due to multiple pump-to-compressor transitions
        at cold ambient air temperature."
    ::= { lgpFlexConditionsWellKnown 6798 }

lgpCondId6799PumpBoardFirmwareUpdateRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Mismatch of pump board firmware.  All pump boards must be running
        the same firmware version."
    ::= { lgpFlexConditionsWellKnown 6799 }

lgpCondId6800PumpControlBoardIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump is shut down due to a pump control board issue.  Control
        board must be rebooted."
    ::= { lgpFlexConditionsWellKnown 6800 }

lgpCondId6801PumpInvalidDataShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump is shut down due to invalid data."
    ::= { lgpFlexConditionsWellKnown 6801 }

lgpCondId6802PumpInputPressureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump input refrigerant pressure sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6802 }

lgpCondId6803PumpInputTemperatureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump input refrigerant temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6803 }

lgpCondId6804PumpOutputPressureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump output refrigerant pressure sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6804 }

lgpCondId6805PumpOutputTemperatureSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump output refrigerant temperature sensor is disconnected or the
        signal is out of range."
    ::= { lgpFlexConditionsWellKnown 6805 }

lgpCondId6806PumpCommunicationLost  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Communication with pump unit has been lost."
    ::= { lgpFlexConditionsWellKnown 6806 }

lgpCondId6807PumpRemoteShutdown  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump is shut down by a remote signal."
    ::= { lgpFlexConditionsWellKnown 6807 }

lgpCondId6808PumpUSBEthernetPortIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump control board USB or Ethernet interface has failed."
    ::= { lgpFlexConditionsWellKnown 6808 }

lgpCondId6809PumpStartupFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Multiple attempts to start the pump have failed."
    ::= { lgpFlexConditionsWellKnown 6809 }

lgpCondId6810PumpInverterFailure  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump inverter is reporting a failure."
    ::= { lgpFlexConditionsWellKnown 6810 }

lgpCondId6811PumpTVSSIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump Transient Voltage Surge Suppressor or Surge Protection Device
        has failed."
    ::= { lgpFlexConditionsWellKnown 6811 }

lgpCondId6812PumpHighSuperheat  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Pump inlet refrigerant superheat temperature is too high, or the
        pump has been running too long with the condenser fan off."
    ::= { lgpFlexConditionsWellKnown 6812 }

lgpCondId6813CondenserHighAmbientAirTempDelta  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "The difference between condenser measured ambient air temperatures
        has been  too large for an extended period of time."
    ::= { lgpFlexConditionsWellKnown 6813 }

lgpCondId6814CondenserLeeTempOptionMismatch  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Lee-Temp option configured at a condenser unit does not match Lee
        -Temp option configured at the control unit."
    ::= { lgpFlexConditionsWellKnown 6814 }

lgpCondId6815CondenserBoardFirmwareUpdateRequired  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Mismatch of condenser board firmware.  All condenser boards must
        be running the same firmware version."
    ::= { lgpFlexConditionsWellKnown 6815 }

lgpCondId6816CondenserToPumpHighRefrigerantTempDelta  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Temperature delta between the condenser output refrigerant and
        pump inlet refrigerant is too large."
    ::= { lgpFlexConditionsWellKnown 6816 }

lgpCondId6817CondenserRefrigerantTypeMismatch  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Refrigerant type configured at condenser unit does not match
        refrigerant type configured at the control unit."
    ::= { lgpFlexConditionsWellKnown 6817 }

lgpCondId6818ExternalSupplyFluidHighTemperature  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply fluid temperature has exceeded a threshold, as indicated by
        an external input signal."
    ::= { lgpFlexConditionsWellKnown 6818 }

lgpCondId6819ExternalSupplyFluidTempSensorIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply fluid temperature sensor is disconnected or the signal is
        out of range, as indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 6819 }

lgpCondId6822AuditLogUpdate  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Audit log has been updated."
    ::= { lgpFlexConditionsWellKnown 6822 }

lgpCondId6824ExternalSupplyFluidFlowIssue  OBJECT-IDENTITY
    STATUS current
    DESCRIPTION
        "Supply fluid flow issue, as indicated by an external input signal."
    ::= { lgpFlexConditionsWellKnown 6824 }

END